Check code
Location
of
detection
Description
System status
Check code detection
condition(s)
Check items (locations)
• Check connector
connection and wiring on
compressor P.C. board.
• Check for failure in
compressor (layer
shortcircuit).
• Check for failure in outdoor
P.C. board ( Compressor).
IPM,
Compressor
shortcircuit
protection
trouble
Compressor
P.C. board
1
∗
: Compressor
1 side
2
∗
: Compressor
2 side
All stop
Overcurrent is momentarily
detected during startup of
compressor.
P26
P26
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
• Check wiring and
connector connection.
• Check for compressor
layer short-circuit.
• Check for failure in
compressor P.C. board.
Compressor
position
detection circuit
trouble
Compressor
P.C. board
1
∗
: Compressor
1 side
2
∗
: Compressor
2 side
All stop
Position detection is not
going on normally.
P29
P29
• Check indoor P.C. board.
Other indoor
trouble
(group follower
unit trouble)
Indoor unit
Stop of
corresponding
unit
There is trouble in other
indoor unit in group,
resulting in detection of
E07/L07/L03/L08.
P31
—
—
• Check fan motor.
• Check for failure in fan
P.C. board.
• Check connection of fan
motor connector.
• Check power voltage of
the main power supply.
Outdoor fan
P.C. board
trouble
Fan INV.
P.C. board
1
∗
: Fan P.C.
board 1
2
∗
: Fan P.C.
board 2
All stop
Protected operation of Fan
inverter P.C. board
P22
P22
- 148 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...