Ye
s
No
Ye
s
No
[F03]
Check code
Check code name
Cause
Indoor
TC1 sensor trouble
TC1 sensor Open/Short-circuit
Is TC1
sensor connector
(CN100: Brown) on indoor
P
.C. board normally
connected?
Are characteristics
of
TC1 sensor resistance
value normal?
Correct connection of
connector
.
Replace TC1
sensor
.
Replace indoor main P
.C. board.
* See
“Indoor unit temperature
sensor characteristics” on “9-6. SensorCharacteristics”.
[F10]
Check code
Check code name
Cause
Indoor TA
/TSA
sensor trouble
T
A
sensor Open/Short-circuit
This trouble code
means detection
of Open/Short-circuit of TA
sensor. Check disconnection of circuit for connection
of connector (TA /TSA sensor :
CN104, Yellow) and characteristics of sensor resistance value.
(See “Indoor unit
temperaturesensor characteristics” on “9-6. Sensor Characteristics”.)
If
se
nso
r is
nor
m
al
, re
place
ind
oo
r P
.C
.
b
oa
rd
.
[F29]
(Power ON)
(Repetition)
(Approx. 3 minutes)
(Approx. 1 minute)
Indoor other trouble
Indoor P
.C. board trouble
This trouble is detected during operation of air conditioner of IC10 non-volatile memory (EEPROM) on
indoor unit P
.C.board. Replace service P
.C. board.
* If EEPROM was not inserted when power was turned on or it is absolutely impossible to read/write
EEPROM data, the automatic address mode is repeated.
[SET
DA
T
A]
is displayed
on remote
controller
.
[SET
DA
T
A]
disappears.
LED (D02) 1Hz
flashes for approx.
10 seconds on
indoor unit P
.C.
board.
Reboot (Reset)
Check code
Check code name
Cause
[F30]
Check code
Check code name
Cause
Occupancy sensor trouble
1.Occupancy sensor trouble
2. Indoor P.C. board trouble
(4-way cassette type)
Is connection
of the occupancy
sensor connector
(CN214) nor
mal?
Correct the connector
connection.
Is DN code [B5] setup?
By the wired remote
controller
, change the
enab
le DN code [B5] from
[0000]
→
[0001]
Replace the indoor
P
.C
. board (MCC-1643).
NO
YES
Is the Occupancy
sensor unit nor
mal?
Replace the Occupancy
sensor unit
NO
YES
NO
YES
- 155 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...