No. Part name
Procedure
Remarks
⑤
Drain pump
Float switch
1. Detachment
1) Perform works until opening of the electric parts box
cover in works of 1 of
②
.
2) Remove the connectors which connect to float switch
of the drain pump from the control P.C. board.
CN34 : Float switch (3P, Red)
CN504 : Drain pump (2P, White)
3) Loosen the fixing screws (2 positions) of the check cover
and then take out the check cover.
(To the check cover, the drain pump and float switch are
attached.)
4) Pick up the hose band, shift from the pump connecting
part, remove the drain hose and then remove the check
cover.
5) Remove screws which fix the drain pump assembly and
then remove the drain pump assembly. (Ø4 x 10, 3 pcs.)
6) Remove the resin nut switch and then remove the float
switch from the fixing plate.
2. Attachment
1) Using the removed screws, fix the drain pump assembly
as original.
2) Using the removed resin nut, fix the float switch as
original.
3) Connect the drain hose as original and then attach the
hose band.
Entering part
Fixing screws
Screw
Check cover
Resin nut
Drain pump
Float switch
Drain hose
Hose band
NOTE
Insert the drain hose to the end of the drain pump.
4) Connect the drain pump and the float switch wiring as
original and close the electric parts box cover for fixing.
Be sure to perform wiring in the electric parts box as
original.
5) Enter the corners (2 positions) of the check cover in the
entering part and then fix it using fixing screws
(2 positions).
Drain hose
Connector
position
CN34
CN504
- 196 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...