⑦
Fan motor, fan
1. Detachment
1) Remove the electric parts box cover.
(see the 1. of
①
)
2) Disconnect the leads for the fan motor from the fan
control board.
CN703 : Fan motor (leads : Black), W
CN704 : Fan motor (leads: White), V
CN705 : Fan motor (leads: Red), U
Note
Unlock the locks on the housing to remove
the connector.
3) Remove the ferrite core from the leads of the fan
motor.
Note
After replacing the fan motor, re-connect
motor leads with the ferrite core rang
around the leads by 1 loop.
4) Remove the bottom plate (suction side).
(see the 1. of No.
⑥
)
5) Remove the screws A (8 pcs), and loosen the screws
B (2 pcs). Don’t remove the screws B (2 pcs) since
they are used as hooks later.
6) Remove the fan assembly.
Fan assembly
Caution
The fan assembly weighs 30 kg.
Be sure that the work is performed by two
persons or more with great care.
7) Remove the screws C (8 pcs).
8)
9)
Loosen the hexagonal bolts (2 pcs) which secure the
fan to the motor shaft, and remove the fan from the
motor shaft.
Remove the screws D (4 pcs) for the fan case, and
remove the fan after removing the nose plate.
10) Remove the earthing screw for the fan motor.
11) Remove the screws E (2 pcs), and remove the motor
anchor plate and the fan motor.
Fan motor leads
CN703
CN704
CN705
Ferrite core
Screw B
Screw A
Screw C (also on the other side)
Fan case
Hexagonal bolt
Screw D
Nose plate
Motor anchor plate
Earthing screw
Fan motor
Screw E
- 217 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...