No.
Part name
P
rocedure
s
Remarks
Vertical louver
assembly
9
10
1) Follow the procedure item 3 and 8 .
2) Remove 2 fixing screws from the base
vertical louver then remove the vertical louver
assembly from the body back.
Vertical louver
Screw
Screw
Cover motor VT
assembly
1) Follow the procedure item 3 , 8 and 9 .
2) Remove 4 fixing screws from the body back.
then remove cover motor VT assembly from
rear side of main unit.
Screws
Screws
Cover motor VT
assembly (L)
Cover motor VT
assembly (R)
Back body
Heat exchanger
Bearing base
Cross flow fan
Bearing base
1) Follow the procedure item 3 .
2) Remove 4 fixing screws from the bearing
base, then remove it from the main unit.
11
<Caution at assembling>
-- If the bearing is out from the housing, push it
into the specified position, then incorporate it
in the main unit.
Bearing base
Bearing
Cross flow fan
Heat exchanger
Cross flow fan
12
1) Follow the procedure item 9 and
11
.
2) Loosen the set screw of the cross flow fan.
Vertical louver Hexagon screw driver
Cross flow fan
3)) Lift up the heat exchanger follow the figure.
Pull out the left hand side until the cross flow
fan released from the shaft of the fan motor
and then pull out the lower side of heat
exchanger follow the figure.
<To re-installation>
1) To incorporate the fan motor and the motor
into the position in the following figure.
- Install the cross flow fan so that the right
end of the 1st joint from the right of the
Cross flow fan is keep 3.5mm from closed
wall of the main unit.
- 243 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...