No.
10
Item
Refrigerant (Oil)
recovery control in
heating operation
Outline of specifications
Indoor units during stop/thermostat OFF or FAN
operation perform following controls when a refrigerant
(compressor oil) recovery signal is received from
outdoor unit at the heating operation,
(1) Opening the indoor unit PMV at constant valve
opening. (For a maximum of about 20 minutes)
(2) TC2 temperature is detected to close its PMV.
Also, the fan, louvers, drain pump may operate for
about one minute after recovery control finished
depending on indoor unit types, until the number
of recovery control reaches the predetermined
number.
NOTE
The PMV, indoor fan, or louvers may operate through
the outdoor unit instruction.
For its detail, refer to the outdoor unit service guide.
Remarks
Indoor unit during cooling
thermostat OFF or FAN
operation stops the indoor fan
and displays "Operation
standby ".
Control is performed per one
hour or when the outdoor unit
determines its need.(It varies
depending on the indoor units
connected.)
• A model with a drain pump :
4-way
Concealed Duct
High Static Duct
Fresh air
Compensation
control for short
intermittent
operation
Drain pump
control
Elimination of
retained heat
HA control
1) For 3 minutes after start of operation, the opera-
tion is forcedly continued even if the unit enters in
Thermostat-OFF condition.
2) However the thermostat is OFF giving prior to
COOL/HEAT selection, READY
for operation
and protective control.
1) In cooling operation (including DRY operation),
this control anytime operates the drain pump.
2) During operation of the drain pump, if the float
switch operates, the drain pump continuously
operates and a check code is issued.
3) During stop status of the drain pump, if the float
switch operates, the thermostat is forcedly off and
this control operates the drain pump. After
continuous operation of the float switch for approx.
5 minutes, this control stops the operation and a
check code is issued.
1) When the unit stopped from [HEAT] operation, the
indoor fan operates with [L] for approx. 30 seconds.
1) ON/OFF operation is available by input of HA
signal from the remote site when connected to
remote controller or the remote ON/OFF interface.
2) HA control outputs ON/OFF status to HA terminal.
3) The input-output specifications of HA conform to
JEMA standard.
Usually the priority is given to
5 minutes at outdoor controller
side.
Check Code [P10]
When using HA terminal
(CN61) for the remote ON/
OFF, a connector sold sepa-
rately is necessary.
In case of group operation, use
the connector to connect HA
terminal to either master or
follower indoor unit.
11
12
13
14
9
Refrigerant (Oil)
recovery control in
cooling operation
Indoor units during stop/thermostat OFF or FAN
operation perform following controls when a refrigerant
(compressor oil) recovery signal is received from
outdoor unit at the cooling operation,
(1) Opening the indoor unit PMV at constant valve
opening. (For a maximum of about 4 minutes)
(2) Operating the drain pump for about one minute,
during recovery control and after the control
finished.
Also, indoor unit fan or louvers may operate
depending on the indoor unit type.
Control is performed per two
hours or when the outdoor unit
determines its need.(It varies
depending on the indoor units
connected.)
- 73 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...