No.
19
Item
Louver control
(Continued):
Outline of specifications
<<Selection of Swing mode>>
• For the Swing mode, the following three types of modes
are selectable and settable by keeping Swing/Direction
SWING/FIX
button pushed for 4 seconds or more on the remote
controller.
1) Standard (4 pieces: same phase) swing
→
Data: [0001 (At shipment)]
When Swing operation is selected, four louvers align at
the horizontal discharge position and then start the
Swing operation at the same time.
2) Dual swing
→
Data: [0002]
When operation is selected, the louvers of louver No.
[01] and [03] move to the horizontal discharge position,
the louvers of louver No. [02] and [04] move to the
downward discharge position and then start the Swing
operation at the same time.
3) Cycle swing
→
Data: [0003]
When operation is selected, the louver No. [01] moves to
the horizontal discharge position, [03] to the downward
discharge position, [02] and [04] to the middle position
and then start the Swing operation at the same time.
• Three types of the swing modes can be also selected
and set by the setup data of Item code (DN) [F0].
• In case of selecting the Swing mode, “Dual swing” or
“Cycle swing”, the following numerals is displayed at
the center of the remote controller screen for approx.
3 seconds when
SWING/FIX
button was pushed to select
[SWING]. (No display for the standard swing)
Remarks
Carry out setting operation
during stop of the unit;
otherwise the unit stops
operation.
Dual swing
Cycle swing
<<Louver lock (Louver fix)>>
• For the air direction setup for each discharge port, the louver
position can be locked during the normal operation.
• An arbitrary air direction of an arbitrary louver can be
registered and set by keeping
UNIT
LOUVER
button pushed for
4 seconds or more on the remote controller.
• The louver lock can be set by registering the setup data to
Item code (DN) [F1] to [F4] according to the following table.
Carry out setting operation
during stop of the unit;
otherwise the unit stops
operation.
Alternate lighting
(0.5 sec.)
Alternate lighting
(0.5 sec.)
F1
F2
F3
F4
Objective louver No.
01
02
03
04
Setup data
0000: Release (At shipment)
0001: Horizontal discharge position
~
0005: Downward discharge position
For the setting operation,
refer to [How to set up type
of the swings] in Item
“7 APPLIED CONTROL”
CODE No.
- 76 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...