. Method to set indoor unit function DN code
(When performing this task, be sure to use a wired remote controller.)
Procedure
Be sure to stop the air conditioner before making settings
<RBC-AMT
>
1
Push the
+
+
buttons simultaneously and hold for at
least 4 seconds.
The unit No. displayed first is the address of the header indoor unit in group
control.
Then the fan and louver of the selected indoor unit move.
2
Each time the
UNIT LOUVER
button (left side of the button) is pressed,
one of the indoor unit Nos. under group control is displayed in
turn. Then the fan and louver of the selected indoor unit move.
3
Use the
TEMP.
button to select the CODE No. (DN code) of the
desired function.
4
Use the
button to select the desired SET DATA
associated with the selected function.
5
Push the
button. (The display changes from flashing to
steady.)
• To change the selected indoor unit, go back to step
2
.
• To change the selected function, go back to step
3
.
6
When the
button is pushed, the system returns to normal
off state.
TEMP.
ON / OFF
SET
TIME
TEST
FILTER
RESET
CL
SAVE
SWING/FIX
VENT
UNIT LOUVER
CODE No.
UNIT No.
R.C.
No.
TIMER SET
MODE
FAN
SET DATA
TEST
SETTING
00 01
1-1
10
5
4
1
2
6
3
<RBC-ASCU11-
>
3,6
4,5 1
7
2,4,5
Indoor unit No.
1
Push and hold menu button and [
] setting button simultaneously for 10 seconds or more.
• After a while, the display flashes as shown in the figure. “ALL” is displayed as indoor unit numbers during
initial communication immediately after the power has been turned on.
2
Each time [
] [
] setting button is pushed, indoor unit numbers in the group control
change cyclically. Select the indoor unit to change settings for.
• The fan of the selected indoor unit runs . The indoor unit can be confirmed for which to change settings.
- 98 -
Summary of Contents for MMC-UP0151HP-E
Page 41: ...2 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 41 ...
Page 42: ...MMC UP0241HP E TR MMC UP0271HP E TR 6 4 12 7 42 ...
Page 43: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 43 ...
Page 58: ...3 WIRING DIAGRAMS 3 1 4 way cassette type MMU UP HP E TR 58 ...
Page 59: ...3 2 Ceiling type MMC UP HP E TR 59 ...
Page 60: ...3 3 Concealed Duct Standard type MMD UP BHP E TR 60 ...
Page 61: ...3 4 Concealed Duct High Static Pressure type MMD UP HP E TR 61 ...
Page 62: ...Concealed Duct High Static Pressure type MMD UP HP E TR 62 ...
Page 63: ...3 5 Concealed Duct High Static Pressure fresh air intake type MMD UP HFP E TR 63 ...
Page 65: ...3 7 High wall type MMK UP HP E TR 65 ...
Page 249: ...MMU UP0361HP E TR MMU UP0481HP E TR MMU UP0561HP E TR 268 267 213 214 249 ...
Page 252: ...12 2 Ceiling type MMC UP0151HP E TR MMC UP0181HP E TR 025 024 252 ...
Page 254: ...MMC UP0241HP E TR MMC UP0271HP E TR 029 028 254 ...
Page 256: ...MMC UP0361HP E TR MMC UP0481HP E TR MMC UP0561HP E TR 051 028 027 256 ...
Page 261: ...MMD UP0151BHP E TR MMD UP0181BHP E TR 240 239 238 233 235 261 ...
Page 263: ...MMD UP0241BHP E TR MMD UP0271BHP E TR MMD UP0301BHP E TR 240 239 238 233 235 263 ...
Page 265: ...MMD UP0361BHP E TR MMD UP0481BHP E TR MMD UP0561BHP E TR 240 239 238 233 235 265 ...