background image

– 3 –

SMMS Slim Duct Type

Installation Manual

SMMS Slim Duct Type

Installation Manual

1

Precautions for Safety

The manufacturer shall not assume any liability for the damage caused by not observing the description of this 
manual.

WARNING

General

• Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions 

to install the air conditioner.

• Only a qualified installer or service person is allowed to do installation work. Inappropriate installation may result in 

water leakage, electric shock or fire.

• Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally 

high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or 
an injury to your body.

• Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the 

OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with 
the interior parts. Only a qualified installer(*1) or qualified service person(*1) is allowed to remove the intake grille of 
the indoor unit or service panel of the outdoor unit and do the work required.

• Before carrying out the installation, maintenance, repair or removal work, set the circuit breaker to the OFF position. 

Otherwise, electric shocks may result.

• Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work 

is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.

• Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of 

50 cm or more or to remove the intake grille of the indoor unit to undertake work.

• Wear protective gloves and safety work clothing during installation, servicing and removal.
• Do not touch the aluminium fin of the unit. You may injure yourself if you do so. If the fin must be touched for some 

reason, first put on protective gloves and safety work clothing, and then proceed.

• Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor 

unit and result in injury.

• When work is performed at heights, use a ladder which complies with the ISO 14122 standard, and follow the 

procedure in the ladder’s instructions. Also wear a helmet for use in industry as protective gear to undertake the work.

• Before cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a 

“Work in progress” sign near the circuit breaker before proceeding with the work.

• Before working at heights, put a sign in place so that no-one will approach the work location, before proceeding with 

the work. Parts and other objects may fall from above, possibly injuring a person below. While carrying out the work, 
wear a helmet for protection from falling objects.

• The refrigerant used by this air conditioner is the R410A.
• The air conditioner must be transported in stable condition. If any part of the product is broken, contact the dealer.
• When the air conditioner must be transported by hand, carry it by two or more people.
• Do not move or repair any unit by yourself. There is high voltage inside the unit. You may get electric shock when 

removing the cover and main unit.

Selection of installation location

• When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration 

of refrigerant leakage occur in the room does not exceed the critical level.

• Do not install in a location where flammable gas leaks are possible. If the gas leak and accumulate around the unit, 

it may ignite and cause a fire.

• To transport the air conditioner, wear shoes with additional protective toe caps.
• To transport the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if 

the bands should break.

• Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive 

electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.

• Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise 

it may cause imperfect combustion.

Installation

• Suction duct length must be longer than 850 mm.
• When the indoor unit is to be suspended, the designated hanging bolts (M10 or W3/8) and nuts (M10 or W3/8) must 

be used.

• Install the air conditioner securely in a location where the base can sustain the weight adequately. If the strength is 

not enough, the unit may fall down resulting in injury.

• Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may 

cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other trouble.

• Carry out the specified installation work to guard against the possibility of high winds and earthquake. If the air 

conditioner is not installed appropriately, a unit may topple over or fall down, causing an accident.

• If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas 

comes in contact with fire, noxious gas may generate.

• Use forklift to carry in the air conditioner units and use winch or hoist at installation of them.
• Helmet must be worn to protect your head from falling objects.

 

Especially, when you work under an inspection opening, helmet must be worn to protect your head from falling 
objects from the opening.

• The unit can be accessed from the service panel shown in the figure.

Refrigerant piping

• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor 

is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is 
over pressurized, which may cause a injury.

• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a 

crack in the flare nut after a long period, which may result in refrigerant leakage.

• After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows 

near a fire source, such as a cooking range, noxious gas may be generated.

• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge 

the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge 
the air completely may cause the air conditioner to malfunction.

• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.

Electrical wiring

• Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air 

conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the 
work properly may result in electric shocks and / or electrical leaks.

• To connect the electrical wires, repair the electrical parts or undertake other electrical jobs, wear gloves to provide 

protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks. 
Failure to wear this protective gear may result in electric shocks.

• Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and 

laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, 
smoking and / or a fire.

• Connect earth wire. (Grounding work) 

 

Incomplete grounding causes an electric shock.

• Do not connect earth wires to gas pipes, water pipes, and lightning conductor or telephone earth wires.
• After completing the repair or relocation work, check that the earth wires are connected properly.
• Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local 

regulations and laws.

• Install the circuit breaker where it can be easily accessed by the agent.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances the power wire must not be extended. Connection trouble in the places where the wire is 

extended may give rise to smoking and / or a fire.

• Electrical wiring work shall be conducted according to law and regulation in the community and installation manual.

 

Failure to do so may result in electrocution or short circuit.

5-EN

6-EN

+00EH99879301_01EN.book  Page 3  Tuesday, March 15, 2011  8:42 PM

Summary of Contents for MMD-AP0074SPH-E

Page 1: ...sh Indoor Unit Model name Slim Duct Type MMD AP0074SPH E MMD AP0094SPH E MMD AP0124SPH E MMD AP0154SPH E MMD AP0184SPH E AIR CONDITIONER MULTI TYPE Installation Manual 00EH99879301_01EN book Page 1 Tuesday March 15 2011 8 42 PM ...

Page 2: ... piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructe...

Page 3: ...pair of outdoor unit Gloves to provide protection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get burn...

Page 4: ...ance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation Suction duct length must be longer than 850 mm When the indoor unit is to be suspended the designated hanging bolts M10 or W3 8 and nuts M10 or W3 8 must be used Install the air conditioner securely in a location where the base can sustain the weight adequately If th...

Page 5: ...er It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire electric shocks injury water leakage noise and or vibration may result When carrying out the pump down work shut down the compressor before disconnecting the refrigerant pipe Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or oth...

Page 6: ... trouble in the air conditioner or noise may adversely affect the equipment s operation Locations where there is anything under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inv...

Page 7: ...erm setup of the filter sign Notification of filter cleaning of the remote controller can be changed according to the condition of installation For setup method refer to Filter sign setting in the Applicable controls of this Manual Remove the cover plate and then fix it to the bottom surface Do surely hooking to the main unit Main unit after remover Air filter Main unit Air filter Force Remove the...

Page 8: ... 103 21 20 40 359 372 422 502 19 21 21 163 Ø 9 2 31 Installation of hanging bolt Consider the piping wiring after the unit is hung to determine the location of the indoor unit installation and orientation After the location of the indoor unit installation has been determined install hanging bolts For the dimensions of the hanging bolt pitches refer to the external view When a ceiling already exist...

Page 9: ...10 Nut W3 8 or M10 8 m or less 5 Drain Piping CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained and apply a heat insulation so as not to cause a dew drop Inappropriate piping work may result in water leakage in the room and wet of furniture Piping Heat insulating material Require the following materials for piping and heat insulating at site ...

Page 10: ...e and hose band for connecting the drain hose to the clear drain socket If applying the adhesive socket will be damaged and cause water leakage Align the attached hose band to the end of hose set the tightening position upward and then tighten it Flexible hose Accessory Socket for VP25 vinyl chloride pipe locally procured Drain pipe connecting port Hard socket VP25 vinyl chloride pipe locally proc...

Page 11: ...ts and seams of the heat insulator upward to avoid water leakage Wrap the attached heat insulator seamlessly from the surface of the indoor unit Flexible hose Hose band Attached heat insulator Heat insulator to be procured locally Hard vinyl chloride pipe 6 Duct Design Arrangement Unit mm Referring to the following dimensions manufacture duct at the local site Under air intake Back air intake 805 ...

Page 12: ...lete heat insulation of the supply air flange and sealing may occur dewing resulted in falling of water drop Flange locally procured Aluminum tape locally procured Aluminum tape locally procured Under surface Cover a screw Heat insulator with sticking material 100 mm width locally procured Aluminum tape locally procured Air discharge side Indoor unit Air intake side Connect a duct to the inside of...

Page 13: ...static pressure 20 Pa External static pressure Pa Air Volume m3 h Filter attached AP007 AP009 AP012 AP015 AP018 0 10 20 30 40 50 60 300 400 500 600 700 Standard air volume 540 m3 h Upper limit of external static pressure 50 Pa High 50 Pa Lower limit of externa static pressure 50 Pa Low 50 Pa High 20 Pa Low 35 Pa Low 20 Pa High 10 Pa Low 10 Pa Upper limit of external static pressure 35 Pa Upper lim...

Page 14: ...0 to 1 5 12 7 15 9 Outer dia of copper pipe A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 9 19 7 Work using double spanner Use the tightening torque levels as listed in the table below Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units...

Page 15: ...e power supply specifications follow to the table below If capacity is little it is dangerous because overheat or burnout may be caused For specifications of the power capacity of the outdoor unit and the power supply wires refer to the Installation Manual attached to the outdoor unit Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from...

Page 16: ...Pass the wires through the bushing of wire connection holes of the indoor unit Keep a margin Approx 100 mm on a wire to hang down the electrical control box at servicing or other purpose The low voltage circuit is provided for the remote controller Do not connect the high voltage circuit Before remove the electrical control box cover remove the cover plate and air filter Remove the cover of the el...

Page 17: ...ange the indoor unit settings The settings are changed by operating the wired remote controller The settings cannot be changed using only a wireless remote controller simple remote controller or group control remote controller by itself so install a wired remote controller separately as well Basic procedure for changing settings Change the settings while the air conditioner is not working Stop the...

Page 18: ... 6 Specify 5d to the CODE No in procedure 3 For the SET DATA of procedure 4 select a SET DATA of the external static pressure to be set up from the following table Change on wired remote controller With a remote controller less system group control Besides the switching method using the wired remote controller as a way to establish the external static pressure switching is also possible by changin...

Page 19: ... Detection temperature shift value 0000 No shift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C SET DATA 0000 0001 Remotecontroller sensor Not used Factory default Used 10Test Run Before test run Before turning on the power supply carry out the following procedure 1 By using 500 V megger check that resistance of 1 MΩ or more exists between the terminal block L to N and the e...

Page 20: ...n finished stop the air conditioner from the wireless remote controller and return Dip switch of the receiver section as before A 60 minutes timer clearing function is attached to the receiver section in order to prevent a continuous test operation Small screw Nameplate Notch M4 25 screw 2 pieces Spacer Receiver unit 11Maintenance Daily maintenance Cleaning of air filter If is displayed on the rem...

Page 21: ... service person Maintenance List Parts Inspection method Heat exchanger Access from inspection opening and remove the access panel Examine the heat exchanger if there is any clogging or damages Fan motor Access from inspection opening and check if any abnormal noise can be heard Fan Access from inspection opening and remove the access panel Examine the fan if there are any waggles damages or adhes...

Page 22: ...he log can be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button used t...

Page 23: ... E03 97 Communication error between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received 04 Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at outdo...

Page 24: ...break down IPDU H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 1d Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 17 Current detect circuit system error IPDU H04 H04 44 Comp 1 case thermo operation I F H05 H05 TD1 sensor miswiring I F H06 H06 20 Low pressure protective operation I F H07 H07 d7 Oil level down detective protection I F H08 H08 01 TK1 sensor err...

Page 25: ...01 Comp 1 side 02 Comp 2 side 03 Comp 3 side AF ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side IC ALT Heat sink overheat error IPDU I F P09 P09 Detected heat storage address 47 ALT No heat storage unit water error Heat storage unit P10 P10 Detec...

Page 26: ... Comp 3 Fan Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display AI NET central control display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending error in TCC LINK central control device TCC LINK C06 Receiving error in TCC LINK central control device TCC LINK C12 Batch alarm...

Page 27: ...United Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMD AP0074SPH E MMD AP0094SPH E MMD AP0124SPH E MMD AP0154SPH E MMD AP0184SPH E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies with the provisions of t...

Page 28: ... air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The standards...

Page 29: ...IGH STATIC 2 0003 F HIGH STATIC 3 0006 External static pressure CODE NO 5d F NO CHANGE F STANDARD 0000 F HIGH STATIC 1 0001 F HIGH STATIC 2 0003 F HIGH STATIC 3 0006 External static pressure CODE NO 5d F NO CHANGE F STANDARD 0000 F HIGH STATIC 1 0001 F HIGH STATIC 2 0003 F HIGH STATIC 3 0006 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in IT...

Page 30: ...EH99879399 00EH99879301_01EN book Page 33 Tuesday March 15 2011 8 42 PM ...

Reviews: