–
72
–
H14
H14
I/F
Compressor 2
case thermo
activation
All stop
Compressor 2 case
thermo was
activated.
Check Compressor 2 case thermo
circuit.
(Connector, Wiring, Circuit board)
Open and check the service valve.
(Gas side, Liquid side)
Check the outdoor PMV clogging
(PMV1, 2).
Check the SV42 circuit.
Check the SV4 circuit (SV41 / 42
miswiring).
Check the opening status of indoor
PMV.
Check the four-way valve error.
Check the refrigerant shortage.
H15
H15
I/F
TD2 sensor
miswiring
(incomplete
insertion)
All stop
Air discharge
temperature of (TD2)
does not increase
despite compressor
2 being in operation.
Check installation of TD2 sensor.
Check connection of TD2 sensor connector
and wiring.
Check resistance characteristics of TD2
sensor.
Check for defect in outdoor P.C. board (I/F).
Check code
Location
of
detection
Description
System status
Error detection
condition(s)
Check items (locations)
Outdoor 7-segment display
Sub-code
Check
code
Main
remote
controller