Setup of outside static pressure
Be sure to set up a tap change based upon the
resistance (outside static pressure) of the duct to be
connected.
To set up a tap change, follow to the basic operation
procedure (
1
→
2
→
3
→
4
→
5
→
6
).
• Specify [5d] to the item code in procedure
3
.
• For the setup data of procedure
4
, select a setup
data of the outside static pressure to be set up from
the following table.
• Select by exchange of short plugs on the indoor
microcomputer P.C. board.
• Short plug position
(CN112, CN111, CN110 from the left)
Short plug position
Set data
0000
0001
0003
Filter sold separately
Standard filter
(At shipment)
Super long life filter
High-efficiency filter (65%)
High-efficiency filter (90%)
Setup data
0000
0001
0003
0006
<Change on wired remote controller>
Outside static pressure
40Pa
Standard (At shipment)
70Pa *1
High static pressure 1
100Pa *2
High static pressure 2
20Pa
High static pressure
*1: 65Pa for Model AP0481BH, AP0561BH
*2: 90Pa for Model AP0481BH, AP0561BH
In case of remote controller-less (Group control)
For setup to the high ceiling, there is selecting method by exchanging the short plugs on the indoor
microcomputer P.C. board as shown in the following table other than selecting method by standard wired remote
controller
(sold separately). Utilize this method for remote controller-less (Group control) case.
∗
However, when the setup to high ceiling has been once exchanged, it is required for returning it to 0000 to
change the short plug to the standard (at shipment) position and rewrite data to the setup data 0000 from the
wired remote controller sold separately though setup to 0001 or 0003 are freely available.
To incorporate a filter sold separately for reference
Short
CN112 CN111 CN110
Open
CN112 CN111 CN110
CN112 CN111 CN110