8-6. Applied control of indoor unit
Control system using remote controller interface (TCB-
IFCB-4E2
)
Wiring and setting
• In the case of group control, the control system functions as long as it is connected to one of the indoor units
(control P.C. board) in the group. If it is desired to access the operation and error statuses of other units,
relevant signals must be brought to it from those units individually.
Control items
(1) Start / Stop input signal
Start / stop of unit
(2) In-operation signa
Output present while unit in normal operation
(3) Error signal Output
present while alarm (e.g. serial communication error or operation of protective
device for indoor / outdoor unit) being activated
Wiring diagram of control system using remote controller interface (TCB-IFCB
-
4E2)
Input
IFCB4E2: No-voltage ON / OFF serial signal
Output
No-voltage contact (in-operation and error indication)
Contact capacity: Max. AC 240 V, 0.5 A
1
2
3
4
5
6
CN61
T10
(Yellow)
1
2
3
4
1
2
3
4
5
6
CN13
CN06
Start/Stop input
ON side
Start signal input
Indoor control P.C. board
TCB-IFCB
-
4E2
COM (GND)
Remote controller sisabling / ending input
In-operation signal output
COM (+12V)
Error signal output
OFF side
Stop signal input
COM
In-operation signal output
Error signal output
Power supply 220-240V