64
–
F01
Heat exchanger temperature sensor (TCJ) error
Indoor unit temperature sensor
errors
F02
Heat exchanger temperature sensor (TC2) error
F03
Heat exchanger temperature sensor (TC1) error
F10
Ambient temperature sensor (TA) error
F11
Discharge temperature sensor (TF) error
F04
Discharge temperature sensor (TD1) error
Outdoor unit temperature
sensor errors
F05
Discharge temperature sensor (TD2) error
F06
Heat exchanger temperature sensor (TE1, TE2) error
F07
Liquid temperature sensor (TL) error
F08
Outside air temperature sensor (TO) error
F12
Suction temperature sensor (TS1) error
F13
Heat sink sensor (TH) error
F15
F16
Wiring error in outdoor high pressure sensor (Pd) and low pressure sensor (Ps)
Outdoor pressure sensor wiring error
Wiring error in heat exchanger sensor (TE1) and liquid temperature sensor (TL)
Outdoor unit temperature sensor wiring / installation error
F22
Outdoor discharge temperature sensor (TD3) error
F23
Low pressure sensor (Ps) error
Outdoor unit pressure sensor
errors
F24
High pressure sensor (Pd) error
F29
Fault in indoor EEPROM
H01
Compressor breakdown
Outdoor unit compressor
related errors
H02
Compressor lockup
H03
Current detection circuit error
H05
Wiring / installation error or detachment of outdoor discharge temperature sensor (TD1)
H06
Abnormal drop in low-pressure sensor (Ps) reading
Protective shutdown of outdoor
unit
H07
Abnormal drop in oil level
H08
Error in temperature sensor for oil level detection circuit (TK1, TK2, TK3, TK4 or TK5)
H15
Wiring / installation error or detachment of outdoor discharge temperature sensor (TD2)
H16
Oil level detection circuit error - Error in outdoor unit TK1, TK2, TK3, TK4 or TK5 circuit
H25
Wiring / installation error or detachment of outdoor discharge temperature sensor (TD3)
L03
Duplicated indoor group header unit
L05
Duplicated priority indoor unit (as displayed on priority indoor unit)
L06
Duplicated priority indoor unit (as displayed on indoor unit other than priority indoor unit)
L07
Connection of group control cable to stand-alone indoor unit
L08
Indoor group address not set
L09
Indoor capacity not set
L04
Duplicated outdoor refrigerant line address
L10
Outdoor capacity not set
L17
Outdoor model incompatibility error
L18
Flow selector units error
L20
Duplicated central control address
L28
Too many outdoor units connected
L29
Error in number of IPDUs
L30
Indoor external interlock error
Light block
Check code
Cause of fault
Alternate blinking
Operation
Timer
Ready
Alternate blinking
Operation Timer
Ready
Operation
Synchronized blinking
Timer
Ready
Operation
Timer
Ready
Blinking
Operation
Synchronized blinking
Timer
Ready
Operation
Synchronized blinking
Timer
Ready