96
–
No. Part name
Procedure
Remarks
⑦
⑧
1. Detachment
1) Remove the drain cap and then extract the drain water
accumulated in the drain pan.
2) Loosen screws which fix the bottom base. (For AP018
3 positions and AP036 2 positions)
Remove the fixing screws(2pcs.)at the center only for
AP036Type.
3) As shown in the right figure, when sliding the bottom
base toward arrow direction,it opens using the hinge
part as a shaft.
4) Hold handle of the drain pan and then pull off slowly.
Drain pan
2. Attachment
1) First hook the thin side of the drain pan to the discharge
port panel and then push in the thick side.
2) Close the bottom base and fix it with screws.
NOTE
When removing the drain cap, be sure to receive drain
water using a bucket, etc.
NG
Do not hold the
drain socket.
CAUTION
When replacing the fan motor, be sure
to exchange the clamp filter with the
fan motor lead wire.
Handle
Discharge port panel
Drain socket
Drain pan
CAUTION
When removing the drain pan, do not hold the
drain socket. (Water leakage may be caused.)
Bottom base
Screw
Fixing screw
Hinge part as shaft
Fan case (upper)
Fan motor,
Fan,
Fan case
~
Continuance from the page in front
~