– 20 –
Accessory parts and Parts to be procured locally
H
Accessory parts
<Separate sold parts>
ON / OFF
TEMP.
Part name
Installation Manual
Heat insulator
Q’ty
1
1
1
4
4
Shape
This manual
Usage
(Be sure to hand over to customers)
For heat insulation of Gas pipe connecting section
For heat insulation of Liquid pipe connecting section
For heat insulation of hanging bracket (AP048)
For heat insulation of hanging bracket (AP072, AP096)
Part name
Standard wired
remote controller
Q’ty
1
Shape
Remarks
Model: RBC-AMT31E
NOTE : Never use a wireless type remote controller even if you have one; otherwise the air conditioner may malfunction.
1
PRECAUTIONS FOR SAFETY
• Ensure that all Local, National and International regulations are satisfied.
• Read this “PRECAUTIONS FOR SAFETY” carefully before Installation.
• The precautions described below include the important items regarding safety. Observe them without fail.
• After the installation work, perform a trial operation to check for any problem.
Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
• Turn off the main power supply switch (or breaker) before the unit maintenance.
• Ask the customer to keep the Installation Manual together with the Owner’s Manual.
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT
DESTROY OZONE LAYER.
The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure
is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil
has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or
refrigerating oil does not enter the refrigerating cycle.
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging
port of the main unit and installation tools are changed from those for the conventional refrigerant.
Accordingly the exclusive tools are required for the new refrigerant (R410A).
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust
does not enter. Moreover, do not use the existing piping because there are problems with pressure-resistance
force and impurity in it.
CAUTION
To Disconnect the Appliance from Main Power Supply.
This appliance must be connected to the main power supply by means of a switch with a contact separation of
at least 3 mm.
5. INSTALLATION MANUAL