Wiring the indoor unit
Be sure to connect the wire while matching the terminal numbers. Incorrect connection causes a trouble.
R(L) S(N)
10
10
30
70
Earth line
Connecting cable
R(L) S(N)
U1 U2 A B
R(L) S(N)
U1 U2 A B
Remote controller wiring
• As the remote controller wire has no polarity, there is
no problem if connections to indoor unit terminal blocks
A and B are reversed.
<MMD-AP0481HFE>
<MMD-AP0721HFE, AP0961HFE>
Wiring between indoor and outdoor units
<Wiring example>
NOTE
An outdoor unit connected with
control wiring between indoor
and outdoor units wire becomes
automatically the header unit.
Terminal block for remote controller
wiring of indoor unit
A
B
Remote controller wire
(Field supply)
Remote
controller unit
A
B
Terminal block
<Wiring diagram>
Address setup
Set up the addresses according to the Installation Manual attached to the outdoor unit
Indoor power supply
220-240V, ~50Hz
220V~60Hz
Outdoor power supply
380V-415V ~ 50Hz
380V ~ 60Hz
Earth leakage
breaker
Header outdoor unit
Remote controller
Pull box
Earth leakage breaker
power switch
Pull box
Pull box
Header outdoor unit
Earth leakage
breaker
Earth
Earth
terminal
U1 U2
U1 U2 U3 U4
L1 L2 L3 N
U5 U6
L N
A B
A B
Control wiring between outdoor units
Control wiring between indoor and outdoor units
Control wiring between indoor units
Outdoor power supply
380V-415V ~ 50Hz
380V ~ 60Hz
Earth
terminal
U1 U2 U3 U4
L1 L2 L3 N
U5 U6
Indoor unit
Indoor unit
Remote controller
Earth
U1 U2
L N
A B
A B
Indoor unit
Indoor unit
Remote controller
Earth
U1 U2
L N
A B
A B
Earth
U1 U2
L N
A B