– 71 –
Check code display list (Outdoor unit)
Check code display
E06
E07
E08
E12
E15
E16
E19
E20
E23
E25
E26
E28
E31
F04
F05
F06
F07
F08
F12
F15
F16
F23
F24
F31
H04
H06
H07
H08
H14
H16
Outdoor 7-segment
Sub-code
No. of indoor units of normal
reception
—
Duplicated indoor unit Nos.
01: Indoor/Outdoor
communication
02: Communication between
outdoor units
—
00: Capacity over
01 ~ : Connected units
00: No center
02: Two or more center units
01: Connected outdoor unit of
other line
02: Connected indoor unit of
other line
—
—
No. of outdoor units of normal
reception
Detection of outdoor unit No.
01: A3-IPDU1 error
02: A3-IPDU2 error
03: A3-IPDU1/2 error
04: Fan IPDU error
05: A3-IPDU1 + Fan IPDU error
06: A3-IPDU2 + Fan IPDU error
07: All IPDU error
—
—
—
—
—
—
—
—
—
—
—
—
—
—
01: TK1 sensor error
02: TK2 sensor error
03: TK3 sensor error
04: TK4 sensor error
—
01: TK1 oil circuit system error
02: TK2 oil circuit system error
03: TK3 oil circuit system error
04: TK4 oil circuit system error
TCC-LINK central
&
Remote controller
E06
(E04)
(E08)
E12
E15
E16
E19
E20
E23
E25
E26
E28
E31
F04
F05
F06
F07
F08
F12
F15
F16
F23
F24
F31
H04
H06
H07
H08
H14
H16
Representative defective position
Decrease of indoor units
Indoor / Outdoor communication circuit
error
Duplicated indoor addresses
Automatic address start error
There is no indoor during automatic
address is operating.
No. of connected indoor units/
Capacity over
No. of center outdoor units error
Connected unit of other line during
operation of automatic address
Sending error of communication
between outdoor units
Duplicated terminal outdoor address setup
Decrease of connected outdoor units
Terminal outdoor unit error
IPDU communication error
Outdoor discharge temp sensor (TD1) error
Outdoor discharge temp sensor (TD2) error
Outdoor heat exchanger temp sensor
(TE1) error
Outdoor liquid temp sensor (TL) error
Outdoor air temp sensor (TO) error
Outdoor suction temp sensor (TS1) error
Outdoor temp sensor (TE, TL) miswiring
Outdoor pressure sensor (Pd, Ps)
miswiring
Low voltage (Ps) sensor error
High voltage (Pd) sensor error
Outdoor EEPROM error
Compressor 1 case thermostat operation
Low-pressure protective operation
Protection for oil level drop detection
Oil level detection temp sensor
(TK1 to TK4) error
Compressor 2 case thermostat operation
Oil level detection circuit system error
Error contents
There is no communication from indoor unit.
(Decrease of connected indoor units)
Signal cannot be sent to indoor unit.
(
→
There is no communication from outdoor unit at indoor side.)
Multiple indoor units having same address exists.
(Detected also at indoor unit side)
Automatic indoor address is operated during setting of
automatic address of another line.
Automatic outdoor address is operrated during setting of
automatic indoor address.
Signal from outdoor unit is not received while automatic
address is operating.
Total capacity of indoor units is over.
(Exceeds the total capacity of outdoor units × 105%)
There is no center outdoor unit in one line or multiple center
outdoor units in one line.
Indoor unit of other line is detected while automatic address is
being set up.
Signal cannot be sent to other outdoor units.
Outdoor addresses manually set are duplicated.
There is no communication from terminal outdoor unit.
(Decrease of connected terminal outdoor units)
Center outdoor unit detects error of terminal outdoor unit.
(For terminal outdoor unit, details are displayed.)
There is no communication of each IPDU (P.C. board) in
inverter box.
Open / Short of discharge temp sensor (TD1) is detected.
Open / Short of discharge temp sensor (TD2) is detected.
Open / Short of heat exchanger temp sensor (TE1) is detected.
Open / Short of outdoor liquid temp sensor (TL) is detected.
Open / Short of outdoor air temp sensor (TO) is detected.
Open / Short of outdoor suction temp sensor (TS1) is detected.
Miswiring on temp sensor (TE, TL) is detected.
Miswiring on outdoor pressure sensor (Pd, Ps) is detected.
Output voltage of low pressure (Ps) sensor is zero.
Output voltage of high pressure (Pd) sensor is zero or
abnormal value was detected during stop of compressor.
Outdoor EEPROM error
(Center unit alarm stops and terminal units continue operation.)
Case thermostat of compressor 1 performs protective operation.
Low-pressure (Ps) sensor detects protective operation.
Protective operation is detected by oil level detection temp
sensor (TK1 to TK4).
Open / Short of oil level detection temp sensor (TK1 to TK4) is
detected.
Case thermostat of compressor 2 performs protective operation.
Temperature change of oil level detection temp sensor
(TK1 to TK4) cannot be detected though compressor started
the operation.