– 8 –
SMMS Concealed Duct High Static Pressure Type
Installation Manual
EN
SMMS Concealed Duct High Static Pressure Type
Installation Manual
Duct design
1
In order to prevent short circuits, design the duct installation, so that the intake and discharge
openings are not adjacent to each other.
2
The indoor unit does not have a built-in air filter. Make sure to set up the filter chamber etc. and
install the air filter (Locally procured). If no air filter is installed, the heat exchanger will be blocked
by dust, which may cause the malfunction of air conditioner or the water leakage.
NOTE
All duct connection between units except outdoor unit must be procured and enforced locally.
Duct hose (with heat insulation)
Flexible duct hanging band
Air discharge chamber
(with heat insulation)
Air discharge port
connecting flange
Indoor unit
High efficiency filter
inserting port
Pre filter
inserting port
Air intake port
connecting flange
Air intake
chamber
Filter
chamber
Electrical control
box
from ground floor
Duct hose
Check port or carrying
in port (600x600)
Check port cap
Ceiling
Air discharge port
Air discharge port
to ground floor
<Duct installation example (First floor))>
5
Fan Characteristics
REQUIREMENT
Add a air volume damper to the air supply duct, and adjust the air volume in the range from 80 % to 120 % of the standard air
volume.
4
4.5
5
5.5
6
6.5
7
7.5
8
3000
3400
3800
4200
2880
3200
3600
4000
4320
5
50
100
150
200
250
300
Standard air volume: 3600 m³/h
High static pressure tap (60 Hz)
Medium static pressure tap (60 Hz)
Low static pressure tap (50 Hz)
Ex
ter
nal stati
c
p
ress
u
re
(Pa)
Air volume (m³/h)
C
u
rr
ent of fan motor (
A
)
Upper limit of air volume
Low static pressure tap (60 Hz)
High static pressure tap (50 Hz)
Medium static pressure tap (50 Hz)
High static pressure tap (50 Hz)
Low static pressure tap (50 Hz)
High static pressure tap (60 Hz)
Medium static pressure tap (50 Hz)
Medium static pressure tap (60 Hz)
Low static pressure tap (60 Hz)
Lower limit of air volume
AP072 type
4
4.5
5
5.5
6
6.5
7
7.5
8
8.5
3400
3800
4200
4600
5000
3360
3600
4000
4400
4800
5040
5
50
100
150
200
250
300
350
External
static pr
es
sure (
P
a)
C
u
rr
ent of fan motor (
A
)
Air volume (m³/h)
Upper limit of air volume
Lower limit of air volume
High static pressure tap (60 Hz)
Medium static pressure tap (60 Hz)
Low static pressure tap (50 Hz)
Standard air volume : 4200 m³/h
Low static pressure tap (60 Hz)
High static pressure tap (50 Hz)
Medium static pressure tap (50 Hz)
High static pressure tap (60 Hz)
Low static pressure tap (50 Hz)
Low static pressure tap (60 Hz)
High static pressure tap (50 Hz)
Medium static pressure tap (50 Hz)
Medium static pressure tap (60 Hz)
AP096 type
15-EN
16-EN
+00EH99879701_01EN.book Page 8 Monday, March 21, 2011 6:12 PM