Manual address setting using the remote control
Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed
and outdoor wiring has not been started (manual setting using the remote control)
Wiring example of 2 refrigerant lines
In the example above, disconnect the remote control connections between the indoor units
and connect a wired remote control to the target unit directly before address setting.
Pair the indoor unit to set and the remote control one-to-one.
Turn on the power.
1
Push and hold the
SET
,
CL
and buttons at the same time for more than 4 seconds.
LCD starts flashing.