Indoor fan motor
trouble
1.
Installation
environment
trouble
2.
Electric parts
trouble
3.
Wiring
trouble
of fan motor connector
4.
Fan motor
trouble
5.
I
ndoor P.C. board
trouble
*
2
: Measure the resistance value of each winding by using the tester
Fan motor inside wiring diagram
Check code name
Check code
[P12]
Cause
Red
White
Black
SWF-340W1000-1
Position
Resistance value
Red - White
2.6 ± 0.3 Ω
White - Black
2.6 ± 0.3 Ω
Black - Red
2.6 ± 0.3 Ω
at
68°F (
20°C
)
YES
NO
YES
*1 : Power relay pin No,
NO
YES
NO
YES
YES
NO
YES
NO
NO
YES
Power supply OFF
If there is any poor connection of
the connector of MCC-1610, or
disconnection of the motor lead.
Remove the motor lead from
CN703,704,705 of MCC-1610
If the fan motor is locked or not.
(Unable to rotate it by hand)
If the winding resistance of the
motor is correct or not.
*2
Measure the power supply voltage
and if the voltage is normal or not.
208-230V
If the power relay operates
normally or not.
(the voltage between power relay
4pin-GND and 6pin-GND are
187-229/207-253V
Correction of the connection
of the connector
Replacement of the motor
Adjustment of the main power
supply on the equipment side
The voltage between
the terminals of CN602
of MCC-1610 is 12V
Replacement of the power relay
Replacement of the MCC-1610
Power supply ON
Replacement of the MCC-1610
NO
Power supply voltage is less than
1
87/207
V
Power supply voltage is more than
229/253
V
The ambient temperature is
normal or not.
Improves the installation
environment
more than
176
°F (80°C)
- 74 -