– 32 –
EN
*1 Inverter quantity information
(Super Modular Multi System i series (SMMS-i))
Trouble detected by central control device
*1 Inverter quantity information
(Super Modular Multi System e and u series (SMMS-e, SMMS-u))
• For details about check codes determined with an Interface P.C board or an Inverter
P.C board, refer to the Installation Manual of the outdoor unit.
No.
Comp. Inverter
Fan
Inverter
Trouble
1
2
3
01
Comp. 1
02
Comp. 2
03
Comp. 1 + Comp. 2
04
Comp. 3
05
Comp. 1 + Comp. 3
06
Comp. 1 + Comp. 3
07
Comp. 1 + Comp. 2 + Comp. 3
08
Fan
09
Comp. 1 + Fan
0A
Comp. 2 + Fan
0B
Comp. 1 + Comp. 2 + Fan
0C
Comp. 3 + Fan
0D
Comp. 1 + Comp. 3 + Fan
0E
Comp. 2 + Comp. 3 + Fan
0F
All
: Inverter trouble
No.
Comp. Inverter
Fan
Inverter
Trouble
1
2
3
01
Comp. 1
02
Comp. 2
03
Comp. 1 + Comp. 2
08
Fan1
09
Comp. 1 + Fan1
0A
Comp. 2 + Fan1
0B
Comp. 1 + Comp. 2 + Fan1
10
Fan2
11
Comp. 1 + Fan2
12
Comp. 2 + Fan2
13
Comp. 1 + Comp. 2 + Fan2
18
Fan1 + Fan2
19
Comp. 1 + Fan1 + Fan2
1A
Comp. 2 + Fan1 + Fan2
1B
All
: Inverter trouble
63-EN
64-EN
Check code
Wireless remote controller
Check code name
Judging device
Central control
device indication
Outdoor unit 7-segment display
Sensor block display of receiving unit
Auxiliary code
Operation
Timer
Ready
Flash
C05
−
−
−
Sending trouble in central control device
Central control device
C06
−
−
−
Receiving trouble in central control device
Central control device
C12
−
−
−
Batch alarm of general-purpose equipment control interface
General-purpose
equipment I/F
P30
(L20)
Differs according to trouble contents of unit with occurrence of alarm
Group control follower unit trouble
Central control device
−
−
(L20 is displayed.)
• Duplication addresses of indoor units in central control device
• With the combination of air conditioning system, the indoor unit may detect
the check code of L20