– 45 –
4
8
Finish
5, 7
6
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
Press to finish
setting
4
Push the TIME / buttons repeatedly to change the value of the indoor unit address in
SET DATA.
Change the value in SET DATA to that of a new address.
5
Push the
SET
button to confirm the new address on SET DATA.
6
Push the
UNIT LOUVER
button (left side of the button) repeatedly to select another address to
change.
Each time you push the button, the indoor unit numbers in a refrigerant line are indicated
one after another. Only the fan and louvers of the selected indoor unit are activated.
Repeat steps
4
to
6
to change the indoor unit addresses so as to make each of them unique.
7
Push the
SET
button.
(All the segments on the LCD display light up.)
8
Push the button to finish the procedure.