7-5. Diagnosis Procedure for Each Check Code
Check code
[E01] / [–]
(Current code / AI-NET)
Check code name
Communication error between
indoor and remote controller
(Detected at remote controller side)
Cause of operation
1. Remote controller inter-unit cable error
2. Indoor power error
3. Indoor P.C. board error
4. Remote controller address setup error
5. Remote controller P.C. board error
Is a group control operation?
Is power of each indoor unit turned on?
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
Is there no disconnection or
connector contact error on harness out
of terminal block of indoor unit?
Is the inter-unit cable of
remote controllers (A/B) normal?
Is power applied to remote controller?
AB terminals: Approx. DC18V
Is setup of two remote controllers
without main remote controller?
Correct inter-unit cable of
remote controller.
Correct connector connection
and check circuit cabling.
Check power connection status of
indoor unit. (Turn on power again.)
Check indoor P.C. board.
Defect
Replace
Change one to main/other to sub.
(Remote controller address connector)
Check remote controller P.C. board.
Defect
Replace
FILE NO. SVM-05052