76
Check code name
[H01] / [1F]
(Current code / AI-NET)
Check code name
Compressor breakdown
Cause of operation
1. Outdoor unit power line error
2. Compressor circuit system error
3. Compressor error
4. Cause of abnormal overload operation
5. IPDU P.C. board error
Sub-code: 01: Compressor 1 side 02: Compressor 2 side
Details of compressor
power connecting section
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
Is power voltage of outdoor unit normal?
Is not it an abnormal overload?
Check IPDU P.C. board.
Is winding resistance
between phases of corresponding
compressor normal? (Note 1)
Does voltage drop occur
when other compressor starts?
Is connection of wiring or connection of
connector on IPDU P.C. board normal?
Correct power line.
Correct connector connection or wiring.
Correct cause of overload.
Compressor error
(Motor burning, etc.)
Note 1
After checking the output, when connecting the compressor
lead again to the compressor terminal, check surely there is
no distortion on the Fasten receptacle terminal.
If it is loosened, caulk it with pinchers, etc and then connect
lead to the terminal firmly.
380 – 415V ± 10%
Take off lead cable of compressor.
1. Check resistance between windings:
It is normal if there are 0.7 to 0.9 .
2. Check insulation between outdoor cabinet and terminal:
It is normal if there are 10M or more.
S
C
R
FILE NO. SVM-05052
Summary of Contents for MMK-AP0072H
Page 125: ...TOSHIBA CARRIER CORPORATION ...