94
Check code name
[P03] / [1E]
(Current code / AI-NET)
Check code name
Discharge temp TD1 error
Cause of operation
1. Service valve of outdoor unit closed
2. Outdoor PMV error
3. TD sensor error
4. Refrigerant shortage, clogging of refrigerant
circuit system
5. 4-way valve error
6. SV4 circuit leakage, misinstallation
Does not discharge
refrigerant gas bypass to suction side
through 4-way valve?
Open service valve fully.
Repair outdoor PMV.
Replace TD1 sensor.
Check 4-way valve.
Correct wiring
Correct installation of valve coil,
or replace SV41 valve.
Are characteristics of
TD1 sensor resistance normal?
Are service valve of gas
and liquid sides fully opened?
Are not indoor units of different
refrigerant circuit connected?
Refrigerant shortage,
clogging, pipe breakage
* Connector CN300, 301 White
* Refer to Outdoor unit temperature
sensor characteristics-4.
(Check there is no pipe breakage, and then recharge the refrigerant.)
(Check with miswiring check
function of outdoor unit.)
Is outdoor PMV normal?
1. Connector connection
2. Cabling
3. Coil
4. Valve body
5. Outdoor I/F P.C. board
SV4 circuit
1. Are not SV41 and SV42 valve
coils installed reversely?
2. IIs there no leakage through
SV41 circuit?
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
FILE NO. SVM-05052