TROUBLESHOOTING
A wired remote controller is necessary for this function.
This function cannot be operate with a wireless remote controller.
n
Confirmation and check
When a trouble occurred in the air conditioner,
the check code and the indoor unit No. appear
on the display part of the remote controller.
The check code is only displayed during the
operation. If the display disappears, operate the
air conditioner according to the following
“Confirmation of error history” for confirmation.
n
Confirmation of error history
When a trouble occurred on the air conditioner,
the trouble history can be confirmed with the
following procedure. (The trouble history is
stored in memory up to 4 troubles.)
The history can be confirmed from both operat-
ing status and stop status.
Procedure
1
When pushing
SET
and
TEST
buttons at the same time
for 4 seconds or more, the following display ap-
pears.
If [Service check
] is displayed, the mode enters
in the trouble history mode.
• [01 : Order of trouble history] is displayed in CODE
No. window.
• [Check code] is displayed in CHECK window.
• [Indoor unit address in which an error occurred] is
displayed in Unit No.
Procedure
2
Every pushing of “TEMP.”
/
button used to
set temperature, the trouble history stored in
memory is displayed in order.
The numbers in CODE No. indicate
CODE No. [01] (latest)
→
[04] (oldest).
REQUIREMENT
Do not push
CL
button because all the trouble
history of the indoor unit will be deleted.
Procedure
3
After confirmation, push
TEST
button to return to
theusual display.
Check code
Indoor unit No. in
which an error occurred.
3
2
1
n
Check method
On the remote controller (Wired remote controller, Central control remote controller) and the interface P.C. board of
the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display
(on the outdoor interface P.C. board) to display the operation is provided.
Therefore the operation status can be known. Using this selfdiagnosis function, a trouble or position with error of the
air conditioner can be found as shown in the table below.
n
Check code list
The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of check from indoor remote controller: See “Wired remote controller display” in the list.
• In case of check from outdoor unit: See “Outdoor 7-segment display” in the list.
• In case of check from indoor unit with wireless remote controller: See “Sensor block display of receiving unit” in the
list.
AI-NET : Artificial Intelligence, IPDU : Intelligent Power Drive Unit
¡
: Lighting,
¤
: Flashing,
l
: Goes off
ALT : Flashing is alternately when there are two flashing LED.,
SIM : Simultaneous flashing when there are two flashing LED.
Check code
Main
remote
controller
display
E01
E02
E03
E04
E06
—
E08
E09
E10
E12
E15
E16
E18
E19
E20
E23
E25
E26
E28
E31
Outdoor 7-segment display
Auxiliary code
—
—
—
—
—
—
—
—
E06
No. of indoor units in which sensor
has been normally received
E07
—
E08
Duplicated indoor addresses
—
—
—
—
01: Indoor/Outdoor communication
E12
02: Communication between
outdoor units
E15
—
E16
00: Capacity over
01 ~: No. of connected units
—
—
E19
00: Header is nothing
02: Two or more header units
E20
01: Outdoor of other line connected
02: Indoor of other line connected
E23
—
E25
—
E26
No. of outdoor units which received
signal normally
E28
Detected outdoor unit number
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 error
E31
04: Fan IPDU error
05: IPDU + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error
Wireless remote controller
Sensor block displa
of receiving unit
Operation
Timer
PRE, DEF.
Flash
¤
l
l
¤
l
l
¤
l
l
l
l
¤
l
l
¤
l
l
¤
¤
l
l
¤
l
l
¤
l
l
¤
l
l
l
l
¤
l
l
¤
¤
l
l
l
l
¤
l
l
¤
l
l
¤
l
l
¤
l
l
¤
l
l
¤
l
l
¤
Check code name
Communication error between indoor and remote
controller (Detected at remote controller side)
Remote controller transmission error
Communication error between indoor and remote
controller (Detected at indoor side)
Communication circuit error between indoor/outdoor
(Detected at indoor side)
Decrease of No. of indoor units
Communication circuit error between indoor/outdoor
(Detected at outdoor side)
Duplicated indoor addresses
Duplicated main remote controllers
Communication error between indoor MCU
Automatic address start error
Indoor is nothing during automatic addressing
Capacity over / No. of connected indoor units
Communication error between indoor units
Outdoor header units quantity error
Other line connected during automatic address
Sending error in communication between outdoor units
Duplicated follower outdoor addresses
Decrease of No. of connected outdoor units
Follower outdoor unit error
IPDU communication error
Judging
device
Remote
controller
Remote
controller
Indoor
Indoor
I/F
I/F
Indoor / I/F
Remote
controller
Indoor
I/F
I/F
I/F
Indoor
I/F
I/F
I/F
I/F
I/F
I/F
I/F