101
EN
TR
SMMS High-Wall Type
Installation Manual
E09
—
—
99
Duplicated master
remote controllers
Remote
controller
E10
—
—
CF
Communication
error between
indoor unit MC
Indoor unit
E12
E12
01:Indoor /
Outdoor units
communication
02:Outdoor /
Outdoor units
communication
42
Automatic address
start error
I/F
E15
E15
—
42
No indoor unit
during automatic
addressing
I/F
E16
E16
00:Capacity
over
01 ~:No. of
connected units
89
Capacity over /
No. of connected
indoor units
I/F
E18
—
—
97, 99
Communication
error between
header and
follower units
Indoor unit
Indoor unit
E19
E19
00:No header
02:Two or more
header units
96
Outdoor header
units quantity error
I/F
E20
E20
01:Outdoor unit
of other line
connected
02:Indoor unit of
other line
connected
42
Other line
connected during
automatic address
I/F
E21
E21
02:No header
unit
00:Multiple
number of
header units
42
Error in number of
heat storage
master units
I/F
E22
E22
—
42
Reduction in
number of heat
storage units
I/F
E23
E23
—
15
Sending error in
communication
between outdoor
units
Error in number of
heat storage units
(trouble with
reception)
I/F
E25
E25
—
15
Duplicated
follower outdoor
addresses
I/F
E26
E26
No. of outdoor
units which
received signal
normally
15
Decrease of No. of
connected outdoor
units
I/F
E28
E28
Detected
outdoor unit
number
d2
Follower outdoor
unit error
I/F
Check code
Wireless remote controller
Check code
name
Judging
device
Wired
remote
controller
display
Outdoor unit 7-
segment display
AI-NET
central
control
display
Sensor block display of
receiving unit
Auxiliary code
Operation
Timer Ready
Flash
1111058901_EN.indb 34
1111058901_EN.indb 34
11/19/14 3:34 PM
11/19/14 3:34 PM