105
EN
TR
SMMS High-Wall Type
Installation Manual
P22
P22
0*:IGBT circuit
1*:Position
detective circuit
error
3*:Motor lock
error
4*:Motor current
detection
C*:TH sensor
error
D*:TH sensor
error
E*:Inverter DC
voltage error
(outdoor unit
fan)
1A
ALT
Outdoor unit fan
IPDU error
Note: Ignore 0 to F
displayed in “*”
position.
IPDU
P26
P26
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
14
ALT
G-TR short
protection error
IPDU
P29
P29
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
16
ALT
Comp. position
detective circuit
system error
IPDU
P31
—
—
47
ALT
Other indoor unit
error
(Group follower
indoor unit error)
Indoor unit
—
—
—
b7
By alarm device
ALT
Error in indoor unit
group
AI-NET
—
—
—
97
—
AI-NET
communication
system error
AI-NET
—
—
—
99
—
Duplicated
network adapters
AI-NET
*1 Number of IPDU
01: Comp. 1
02: Comp. 2
03: Comp. 1 + Comp. 2
04: Comp. 3
05: Comp. 1 + Comp. 3
06: Comp. 2 + Comp. 3
07: Comp. 1 + Comp. 2
+ Comp. 3
08: Fan
09: Comp. 1 + Fan
0A: Comp. 2 + Fan
0B: Comp. 1 + Comp. 2
+ Fan
0C: Comp. 3 + Fan
0D: Comp. 1 + Comp. 3 + Fan
0E: Comp. 2 + Comp. 3 + Fan
0F: Comp. 1 + Comp. 2
+ Comp. 3 + Fan
Check code
Wireless remote controller
Check code
name
Judging
device
Wired
remote
controller
display
Outdoor unit 7-
segment display
AI-NET
central
control
display
Sensor block display of
receiving unit
Auxiliary code
Operation
Timer Ready
Flash
1111058901_EN.indb 38
1111058901_EN.indb 38
11/19/14 3:34 PM
11/19/14 3:34 PM
FILE NO. SVM-1
40
7
8