119
CODE No. table (Please record the objective unit data at field)
DN
01
02
03
06
0C
0d
0F
10
11
12
13
14
1E
28
2A
2b
2E
32
30
89
Item
Filter sign lighting time
Dirty state of filter
Central control address
Heating suction temp. shift
PRE-DEF indication selection
Cooling auto mode existence
Cooling only
Type
Indoor unit capacity (See below table)
Refrigerant line address
Indoor unit address
Group address
Temp. difference of automatic cooling/
heating selecting control points
Automatic restart from power cut
Option input selection (CN80)
Thermo. output selection (T10
)
Input selection (T10
)
Sensor selection
Timer set (Wired remote controller)
Louver selection of cooling
Memo
Be sure to set as 0008
At shipment
0001: 150 hour
0000: Standard
0099: Unfixed
0002: +2°C
0000: Standard
0001: No auto mode
Automatic selection
cooling/heating
by connected
0000: Heat pump
outdoor unit
0008: High wall type
According to capacity type
0099: Unfixed
0099: Unfixed
0099: Unfixed
0003: 3 deg
(Ts ± 1.5)
0000: None
0002: External emergency input
0000: Thermo. ON
0000: Operation input
0000: Available
0000: Available
0000: Standard
Indoor unit capacity (CODE No. [11])
Setup data
0001
∗
0001
0003
Model
Invalid
MMK-AP0074MHP
MMK-AP0094MHP
0005
MMK-AP0124MHP
∗
Initial value of EEPROM installed on the supplied service P.C. board.
FILE NO. SVM-1
40
7
8