Operation suppression zone
Oper
ation star
ts
Set temperature
1 hour
1˚C
2 hours
2˚C
Set temperature
Operation star
ts
Operation
suppression zone
2 hours
1 hour
2˚C
1˚C
No.
16
17
Item
Hi POWER
operation
(Wireless remote
control specific
operations)
ECO timer
operation
(Wireless remote
control specific
operations)
Outline of specifications
When you press the Hi POWER button during cooling,
heating or A operation, the air conditioner will start the
following operation.
• Cooling operation
Performs the cooling operation at 1°C lower than the setting
temperature.
Only when the fan speed before the Hi POWER operation is
not high, the fan speed will be increased.
• Heating operation
Performs the heating operation at 2°C higher than the
setting temperature.
Only when the fan speed before the Hi POWER operation is
not high, the fan speed will be increased.
When you press the ECO button during cooling, heating or A
operation, the air conditioner will start the following operation.
The fan speed display will indicate AUTO and low speed will
be used.
•
Cooling operation
In the operation suppression zone, where capacity is kept to
the minimum, overcooling is prevented by raising the
temperature setting by 1°C after 1 hour and by 2°C after 2
hours of operation.
The room temperature is thus regulated between the
operation suppression zone and the set temperature.
•
Heating operation
In the operation suppression zone, where capacity is kept to
the minimum, overheating is prevented by lowering the
temperature setting by 1°C after 1 hour and by 2°C after 2
hours of operation.
The room temperature is thus regulated between the set
temperature and the operation suppression zone.