Installation Manual
13-EN
– 13 –
13-EN
SMMS High-Wall Type
Installation Manual
Wireless remote controller
4
INSTALLATION OF INDOOR UNIT
WARNING
Install the air conditioner certainly to sufficiently withstand the weight.
REQUIREMENT
be sure to use buffering cloth, etc. to not damage the unit.
parts, etc.
specified.
NO GOOD
range
Indoor unit
Indoor
unit
5
m
5
m
m
5°
45°
45
°
Screen
OK
NO GOOD
1111058602_EN.indd 13
11/24/16 11:41 AM
5
CUTTING A HOLE AND MOUNTING INSTALLATION
PLATE
Cutting a hole
In case of installing the refrigerant pipes from the
rear:
1. Decide the hole position for piping at
180mm from the arrow mark (
) on the
installation plate and drill a hole at a slight
downward slant toward outdoor side. Pipe
hole; dia.65mm: AP015-AP018 type Pipe
hole; dia.80mm: AP024 type
80
65
1111012101
80
65
1111012101
180mm
The center of the pipe hole is above the arrow.
23 mm
dia. 65mm:
AP015-AP018 type
dia. 80mm:
AP024 type
Pipe hole
NOTE
• When drilling a wall that contains a metal lath,
wire lath or metal plate, be sure to use a pipe
hole brim ring sold separately.
Mounting the installation plate
23
dia.65mm
132
170
110
120
300
85
Pipe hole
Indoor unit
Hook
Hook
Anchor bolt holes
Thread
Weight
Pipe hole
(dia. 65mm
dia. 80mm)
Hook
Installation
plate
Mounting
screw
When the installation plate is
directly mounted on the wall
1. Securely fit the installation plate onto the
wall by screwing it in the upper and lower
parts to hook up the indoor unit.
2. To mount the installation plate on a
concrete wall with anchor bolts, utilize
the anchor bolt holes as illustrated in the
above figure.
3. Install the installation plate horizontally in
the wall.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt
hole. Otherwise the unit may fall down and
result in personal injury and property damage.
5mm dia. hole
Clip anchor
(local parts)
Mounting screw
4 × 25
R
Anchor bolt
Projection
15mm or less
NO
GOOD
NO
GOOD
OK
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit
falls.
• In case of block, brick, concrete or similar type
walls, make 5mm dia. holes in the wall.
• Insert clip anchors for appropriate mounting
screws.
NOTE
• Secure four corners and lower parts of the
installation plate with 6 mounting screws to
install it.
23
dia.65mm
132
170
110
120
300
85
Be sure that the installation plate is fix to the wall
with screws to make the indoor unit fit to the wall.
FILE NO. SVM-18070
- 82 -