Function
[Control items]
* For the card switch box that does not involve contact operation described above, convert signals with a relay including a
normally-closed contact.
External contact terminal
Close (Status that card is inserted)
Open (Status that card is taken out)
Manual prohibition release
(Manual operation)
Card Input 1
Manual prohibition
(Operation stop)
Manual prohibition release
(Automatic operation)
Card Input 2
Manual prohibition
(Operation stop)
Operation status continues
(Do nothing)
Card Input 3
Operation status continues and setting temperature
changes
(COOL/DRY: 29ºC, HEAT: 18ºC)
Manual prohibition release
(The status returns to operating condition before
removing the card.)
Card Input 4
Manual prohibition
(Operation stop)
1) To change a setting temperature by changing data at
DN code No. 172 to 174.
2) The operation mode can be set by changing data
(0000, 0001, 0002) at DN code No. 16b.
0000: operation mode is the same at the current mode.
(factory setting default)
0001: operation mode returns to the previous mode when
card was inserted. (in case of the previous mode is
off operation, the operation mode is also off.)
0002: operation mode starts at the same previous mode
when the card was inserted. (the operation mode
is on operation even the previous mode is off
operation.)
See contents below for DN settings and detailed
operations.
Card Input 5
1) To change a setting temperature, fan speed and wind
direction by changing data at DN code No. 16C to 171.
2) The operation mode can be set by changing data
(0000, 0001) at DN code No. 16A.
0000: operation mode is the same at the current mode.
(factory setting default)
0001: operation automatically starts.
See contents below for DN settings and detailed
operations.
[Card input setup.5 Code (DN)]
DN
Item
Description
At shipment
16C Open mode Set temp. (Cool, Dry)
-0015
㧦
-15ºC
to
0060
㧦
60ºC
0027
㧦
27ºC
172 Close mode Set temp. (Cool, Dry)
-0015
㧦
-15ºC
to
0060
㧦
60ºC
0024
㧦
24ºC
173 Close mode Set temp. (Heat)
-0015
㧦
-15ºC
to
0060
㧦
60ºC
0024
㧦
24ºC
174 Close mode Set temp. (Heat)
-0015
㧦
-15ºC
to
0060
㧦
60ºC
0024
㧦
24ºC
16b Close mode Operation
0000
㧦
No change
0001
㧦
Card ON mode operation
0002
㧦
Run operation (Card ON mode setting)
0000
㧦
No change
16A Open mode Operation
0000
㧦
No change
0001
㧦
Run operation
0000
㧦
No change
16d Open mode Set temp. (Heat)
-0015
㧦
-15ºC
to
0060
㧦
60ºC
0020
㧦
20ºC
16E Open mode Set temp. (Auto)
-0015
㧦
-15ºC
to
0060
㧦
60ºC
0024
㧦
24ºC
16F Open mode Fan speed (All operation mode)
0000
㧦
No change 0001
㧦
HH 0002
㧦
H 0003
㧦
L
0000
㧦
No change
170 Open mode Wind direction (Cool, Dry, Fan)
0000
㧦
No change 0001
㧦
F1 0002
㧦
F2 0003
㧦
F3
0000
㧦
No change
171 Open mode Wind direction (Heat)
0000
㧦
No change 0001
㧦
F1 0002
㧦
F2 0003
㧦
F3
0004
㧦
F4
0005
㧦
F5
0000
㧦
No change
- 42 -