Check code
Location
of
detection
Description
System status
Check code detection
condition(s)
Check items (locations)
• Check capacities of indoor
units connected.
• Check combined HP
capacities of indoor units.
• Check HP capacity
settings of outdoor units.
• Check No. of indoor units
connected.
• Check for failure in outdoor
P.C. board (I/F).
I/F
00:
Capacity over
01-:
No. of units
connected
Too many
indoor units
connected
All stop
• Combined capacity of
indoor units is too large.
Note:
If this code comes up
after backup setting for
outdoor unit failure is
performed, perform "No
capacity over detected"
setting.
<"No capacity over detected"
setting method>
Turn on SW103 / Bit 3 on I/F
P.C. board of outdoor header
unit.
For Cooling Only model,
this check code is not
displayed even if it exceeds
the combined capacity of
indoor units.
• More than 128 indoor units
are connected.
E16
E16
• Check remote controller
wiring.
• Check indoor power supply
wiring.
• Check P.C. boards of
indoor units.
Indoor unit
Trouble in
communication
between indoor
header and
follower units
Stop of
corresponding
unit
Periodic communication
between indoor header and
follower units cannot be
maintained.
E18
—
—
Outdoor header unit is
outdoor unit to which indoor-
outdoor tie cable (U1,U2) is
connected.
• Check connection of
indoor-outdoor
communication line.
• Check for failure in outdoor
P.C. board (I/F).
I/F
00:
No header unit
02:
Two or more
header units
Trouble in
number of
outdoor header
units
All stop
• There are more than one
outdoor header units in
one line.
• There is no outdoor header
unit in one line.
E19
E19
Disconnect inter-line tie
cable in accordance with
automatic address setting
method explained in
"Address setting" section.
I/F
01:
Connection of
outdoor unit
from other line
02:
Connection of
indoor unit
from other line
Connection to
other line found
during
automatic
address setting
All stop
Equipment from other line is
found to have been
connected when indoor
automatic address setting is
in progress.
E20
E20
Note:
Do not set outdoor
addresses manually.
I/F
Duplicated
follower outdoor
address
All stop
There is duplication in
outdoor addresses set
manually.
E25
E25
—
• Backup setting is being
used for outdoor units.
• Check power supply to
outdoor unit. (Is power
turned on?)
• Check connection of tie
cables between outdoor
units for bad contact or
broken wire.
• Check communication
connectors on outdoor
P.C. boards.
• Check for failure in outdoor
P.C. board (I/F).
I/F
Address of
outdoor unit
from which
signal is not
received
normally
Signal lack of
outdoor unit
All stop
Outdoor unit initially
communicating normally
fails to return signal for
specified length of time.
E26
E26
• Check power supply to
outdoor units. (Is power
turned on?)
• Check connection of tie
cables between outdoor
units for bad contact or
broken wire.
• Check communication
connectors on outdoor
P.C. boards.
• Check for failure in outdoor
P.C. board (I/F).
• Check termination
resistance setting for
communication between
outdoor units.
Outdooroutdoor
communication
transmission
trouble
I/F
All stop
Signal cannot be transmitted
to other outdoor units for at
least 30 seconds
continuously.
E23
E23
—
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
- 72 -