6. CONTROL OUTLINE
No.
1
2
3
Room temp.
control
Item
When power
supply is reset
Operation
mode selection
Outline of specifications
1) Distinction of outdoor unit
When the power supply is reset, the outdoors are
distinguished and the control is selected according to the
distinguished result.
2) If resetting the power during a problem, the check code is
cleared. After ON/OFF button on the remote control is
pushed to resume operation and the problem persists, the
check code is again displayed on the remote control.
1) The operation mode is selected based on the operation
mode command on the remote control.
1) Adjustment range: Remote control setup temperature (°F [°C] )
Remarks
Wired type
Wireless type
COOL/DRY
64°F [18°C] to 84°F [29°C]
63°F [17°C] to 86°F [30°C]
HEAT
64°F [18°C] to 84°F [29°C]
63°F [17°C] to 86°F [30°C]
2) Using the Item code 06, the setup temperature in heating
operation can be corrected.
Default setting
Unless the sensor of the
remote control is
controlled, there is a
shift in the suction
temperature during
heating operation.
(Code No. [32], “0001”)
Setup data
0
Remote control
command
STOP
FAN
COOL
HEAT
Control outline
Air conditioner stops.
Fan operation
Cooling operation
Heating operation
Setup data
Setup temp.
Correction
0
2
4
6
+0°F
+3.6°F
+7.2°F
+10.8°F
[+0°C]
[+2°C]
[+4°C]
[+6°C]