– 21 –
No.
4
5
Item
Automatic
capacity control
Outline of specifications
1) Based on the difference between TA and TS, the
operation capacity is determined by the outdoor unit.
Remarks
1) Operation with (HH), (H), (L) or [AUTO] mode is carried
out by the command from the remote control.
2) When the fan speed mode [AUTO] is selected, the fan
speed varies by the difference between TA and TS.
<COOL>
Fan speed
selection
TS: Setup temp.
TA: Room temp.
HH > H > L > UL
TA
˚F (˚C)
+3.6 (+2)
TA
˚F (˚C)
+1.8 (+1)
+1.8 (+1)
Ts
Ts
– 1.8 (– 1)
– 1.8 (– 1)
– 3.6 (– 2)
COOL
HEAT
S3
S5
S7
S9
SB
SD
SF
S0
SD
SB
S9
S7
S5
S3
S0
• Thermostat-off control by a wired remote control
sensor is the same as thermostat-off control by an
indoor unit sensor.
• If the fan speed has been changed once, it is not
changed for 3 minutes. However when the air
volume changes the fan speed changes.
• When cooling operation has started, select a
downward slope for the fan speed, that is, the high
position.
• If the temperature is just on the difference boundary,
the fan speed does not change.
Code No. 32
0000: TA sensor of Indoor
unit
0001: TA sensor of wired
remote control
TA ˚F (˚C)
+5.4 (+3.0)
+4.5 (+2.5)
+3.6 (+2.0)
+2.7 (+1.5)
+1.8 (+1.0)
+0.9 (+0.5)
Tsc
– 0.9 (– 0.5)
HH
<HH>
H <HH>
H <HH>
L <H>
L <H>
L <H>
L <L>
< > : Indicate automatic cooling.
D
C
B
A
E
F
G