– 45 –
*1 Only a part of indoor unit types is installed with the discharge air temperature sensor. This temperature is
not displayed for other types.
*2 When the units are connected to a group, data of the header indoor unit only can be displayed.
*3 The first digit of an CODE No. indicates the outdoor unit number.
*4 The upper digit of an CODE No. -4 indicates the outdoor unit number.
1
∗
, 5
∗
... U1 outdoor unit (Header unit)
2
∗
, 6
∗
... U2 outdoor unit (Follower unit 1)
3
∗
, 7
∗
... U3 outdoor unit (Follower unit 2)
*5 Only the CODE No. 9* of U1 outdoor unit (Header unit) is displayed.
CODE No.
Data name
Display format Unit
Remote control display example
Indoor unit data *
2
Outdoor unit individual data 1 *
3
System data
00
01
02
03
04
05
06
08
F3
Room temperature (Use to control)
Room temperature (Remote control)
Indoor suction air temperature (TA)
Indoor coil temperature (TCJ)
Indoor coil temperature (TC2)
Indoor coil temperature (TC1)
Indoor discharge air temperature (TF) *
1
Indoor PMV opening
Filter sign time
×1
×1
×1
×1
×1
×1
×1
×1/10
×1
°C
°C
°F
°F
°F
°F
°F
pls
h
[0027] = 27 °C
[0150]= 1500 pls
[2500] = 2500h
[0080] = 80 °F
CODE No.
Data name
Display format Unit
Remote control display example
U1
10
11
12
13
15
16
17
18
19
1A
1C
1D
1E
1F
U2
20
21
22
23
25
26
27
28
29
2A
2C
2D
2E
2F
U3
30
31
32
33
35
36
37
38
39
3A
3C
3D
3E
3F
High-pressure sensor detention pressure (Pd)
Low-pressure sensor detention pressure (Ps)
Compressor 1 discharge temperature (TD1)
Compressor 2 discharge temperature (TD2)
Outdoor coil temperature (TE1)
Outdoor coil temperature (TE2)
Outdoor coil temperature (TG1)
Outdoor coil temperature (TG2)
Outside ambient temperature (TO)
Suction temperature (TS1)
Suction temperature (TS3)
Temperature at liquid side (TL1)
Temperature at liquid side (TL2)
Temperature at liquid side (TL3)
×10
×10
×1
×1
×1
×1
×1
×1
×1
×1
×1
×1
×1
×1
psi
psi
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
[4350] = 435 psi
[0080]= 80 °F
CODE No.
Data name
Display format
Unit
Remote control display example
90
Heating/cooling recovery controlled
0: Normal
[0010]=Heating recovery controlled
0: Normal
1: Release controlled
92
Discharge temperature release
[0001]=Discharge temperature release controlled
91
Pressure release
[0010]=Pressure release controlled
93
Follower unit release (U2/U3 outdoor units)
[0100]=U2 outdoor unit release controlled
F9
Suction temperature of air to air heat
exchanger (TSA) *
1
×1
°F
[0080]= 80 °F
FA
0A
0B
0C
0D
Outside air temperature (TOA)*
1
No. of connected indoor units
Total horsepower of connected indoor units
No. of connected outdoor units
Total horsepower of outdoor units
×1
×1
×10
×1
×10
°F
unit
ton
unit
ton
[0048]= 48 units
[0215]= 21.5 ton
[0003]= 3 units
[0160]= 16 ton
Outdoor unit individual data 2 *
4
Outdoor unit
individual
data 3 *
5
CODE No.
Data name
Display format Unit
Remote control display example
U1
50
51
52
U2
60
61
62
U3
70
71
72
PMV1 opening
PMV3 opening
PMV4 opening
[0500] = 500pls
[0058] = 58 mode
[0080] = 8 ton
[0024] = 24 °F
[0642] = 64.2rps
[0135] = 13.5A
×1
×1
×1
pls
pls
pls
56
57
59
5A
5B
5D
5E
5F
66
67
69
6A
6B
6D
6E
6F
76
77
79
7A
7B
7D
7E
7F
Compressor 1 revolutions
Compressor 2 revolutions
Outdoor fan mode
Compressor IPDU 1 heat sink temperature
Compressor IPDU 2 heat sink temperature
Outdoor fan IPDU 1 heat sink temperature
Outdoor fan IPDU 2 heat sink temperature
Outdoor unit horsepower
×10
×10
×1
×1
×1
×1
×1
×10
rps
rps
mode
°F
°F
°F
°F
ton
54 64 74
1 fan model : Compressor 2 and Outdoor fan 1 current (I2)
2 fan model : Compressor 2 and Outdoor fan 2 current (I2)
×10
A
53 63 73
1 fan model : Compressor 1 curent (I1)
2 fan model : Compressor 1 and Outdoor fan 1 current (I1)
×10
A
< Based on the SMMS-e >