– 67 –
Main
remote
control
Check code
P22
P22
#0:Element short circuit IPDU
Outdoor fan
IPDU trouble
*Put in Fan
IPDU No. in [#]
mark
All stop
(Sub code: #0)
Fan IPDU over current protection
circuit.
Flow of current equal to or greater
than the specified value is detected
during startup of the fan.
• Check fan motor.
• Check for defect in fan IPDU P.C.
board.
#1:Position detection
circuit trouble
All stop
(Sub code: #1)
Fan IPDU position detection circuit.
Position detection is not going on
normally.
• Check fan motor.
• Check connection of fan motor
• connector.
• Check for defect in fan IPDU P.C.
• board.
#3:Motor lock trouble
All stop
(Sub code: #3)
Gusty wind, an obstruction, or
another external factor.
Speed estimation is not going on
normally.
• Check fan motor.
• Check for defect in fan IPDU P.C.
• board.
#4:Motor current trouble
All stop
(Sub code: #4)
Fan IPDU over current protection
circuit.
Flow of current equal to or greater
than the specified value is detected
during operation of the fan.
• Check fan motor.
• Check connection of fan motor
connector.
• Check for defect in fan IPDU P.C.
board.
#C:TH sensor
temperature trouble
All stop
(Sub code: #C)
Higher temperature than the
specified value is detected during
operation of the fan.
• Check fan motor.
• Check for defect in fan IPDU P.C.
board.
#D:TH sensor short
circuit/release trouble
All stop
(Sub code: #D)
The resistance value of the sensor
is infinite or zero (open or short
circuit).
• Check for defect in fan IPDU P.C.
board.
#E:Vdc voltage trouble
All stop
(Sub code: #E)
Fan IPDU DC voltage protection
circuit.
The DC voltage higher or lower
than the specified value is detected.
• Check power voltage of the main
power supply.
• Check for defect in fan IPDU P.C.
board.
• Check connection of fan IPDU
P.C. board.
P31
—
—
Indoor
unit
Other indoor
trouble
(group follower
unit trouble)
Stop of
corresponding
unit
There is trouble in other indoor
unit in group, resulting in detection
of E07/L07/L03/L08.
• Check indoor P.C. board.
C05
—
—
TCC-LINK TCC-LINK
central control
device
transmission
trouble
Continued
operation
Central control device is unable to
transmit signal.
• Check for defect in central control
device.
• Check for defect in central control
communication line.
• Check termination resistance
setting.
C06
—
—
TCC-LINK TCC-LINK
central control
device reception
trouble
Continued
operation
Central control device is unable to
transmit signal.
• Check for defect in central control
device.
• Check for defect in central control
communication line.
• Check terminator resistor setting.
• Check power supply for devices
at other end of central control
communication line.
• Check defect in P.C. boards of
devices at other end of central
control communication line.
C12
—
—
General-
purpose
device
I/F
Batch alarm
for general-
purpose
device
control interface
Continued
operation
Trouble signal is input to control
interface for general-purpose
devices.
• Check trouble input.
P30
TCC-LINK
Differs according to
nature of alarm-causing
trouble
Group control
follower unit
trouble
Continued
operation
Trouble occurs in follower unit
under group control. ([P30] is
displayed on central remote control.)
• Check check code of unit that has
generated alarm.
(L20 displayed.)
Duplicated
central control
address
Continued
operation
There is duplication in central
control addresses.
• Check address settings.
P26
P26
01: Compressor 1 side
02: Compressor 2 side
IPDU
IPM shortcircuit
protection
trouble
All stop
Overcurrent is momentarily
detected during startup of
compressor.
• Check connector connection and
wiring on A3-IPDU P.C. board.
• Check for defect in compressor
(layer shortcircuit).
• Check for defect in outdoor P.C.
board (A3-IPDU).
P29
P29
01: Compressor 1 side
02: Compressor 2 side
IPDU
Compressor
position
detection circuit
trouble
All stop
Position detection is not going on
normally.
• Check wiring and connector
connection.
• Check for compressor layer
short-circuit.
• Check for defect in A3-IPDU P.C.
board.
Outdoor 7-segment display
Check
code
Sub-code
Location
of
detection
Description
System status
Trouble detection
condition(s)
Check items (locations)