– 17 –
8
Applicable controls
REQUIREMENT
When the air conditioner is used for the first time, it will
take some moments after the power has been turned on
before the remote controller becomes available for
operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses (The automatic
addresses are set up by performing operations on the
outdoor interface circuit board.)
While the automatic addresses are being set up, no
remote controller operations can be performed. Setup
takes up to 10 minutes (usually about 5 minutes).
• When the power is turned on after automatically
address setup, it takes up to 10 minutes (usually about
3 minute) for the outdoor unit to start operating after
the power has been turned on.
Before the air conditioner was shipped from the factory,
all units are set to [STANDARD] (factory default). If
necessary, change the indoor unit settings.
The settings are changed by operating the wired remote
controller.
* The settings cannot be changed using only a wireless
remote controller and simple remote controller by itself
so install a wired remote controller separately as well.
Applicable controls setup
(settings at the site)
Remote controller model name:
RBC-ASCU11-
Basic procedure
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
CAUTION
CAUTION
Set only the Code No. shown in the following table: Do
NOT set any other Code No.
If a Code No. not listed is set, it may not be possible to
operate the air conditioner or other trouble with the
product may result.
1
Push and hold menu button and [
] setting
button simultaneously for 10 seconds or
more.
• After a while, the display flashes as shown in the
figure. "ALL" is displayed as indoor unit
numbers during initial communication
immediately after the power has been turned on.
3,6
4,5 1
7
2,4,5
Indoor unit No.
2
Each time [
] [
] setting button is pushed,
indoor unit numbers in the group control
change cyclically. Select the indoor unit to
change settings for.
• The fan of the selected indoor unit runs . The
indoor unit can be confirmed for which to
change settings.
3
Push OFF timer button to confirm the
selected indoor unit.
4
Push the menu button to make Code No.
[
] flash. Change Code No. [
] with [
]
[
] setting button.
5
Push the menu button to make Set data
[
] flash. Change Set data [
]
with [
] [
] setting button.
6
Push OFF timer button to complete the
setup.
• To change other settings of the selected indoor
unit, repeat from Procedure
4
.
7
When all the settings have been completed,
push ON/OFF button to finish the settings.
(Return to the normal mode)
"
" flashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while "
" is flashing.)
• To change settings of another indoor unit,
repeat from Procedure
1
.
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other machinery to
circulate heat air near the ceiling.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
• Specify
[06]
for the Code No. in Procedure
4
.
• For the set data in Procedure
5
, select the set data
of shift value of detection temperature to be set up
from the following table.
Filter sign setting
According to the installation condition, the filter sign
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
• Specify
[01]
for the Code No. in Procedure
4
.
• Select the set data of filter sign term from the
following table for the set data in Procedure
5
.
• The filter sign may be unavailable depending on the
remote controllers.
Set data
Code No.
Set data
Detection temperature shift value
0000
No shift
(Factory default)
0001
+1°C
0002
+2°C
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C
Set data
Filter sign term
0000
None
0001
150 H
(Factory default)
0002
2500 H
0003
5000 H
0004
10000 H
33-EN
34-EN