– 8 –
Installation space
(Unit: mm)
Reserve sufficient space required for installation or service work.
Filter cleaning sign term setting
The lighting term setup of the filter sign (Notification of filter cleaning) of the remote controller can be changed
according to the condition of installation.
For setup method, refer to “Filter sign setting” in the Applicable controls of this Manual.
200 or
more
100 or more*
10
00 or
mor
e
(Front side)
(Front side)
* For right or left direction piping, take a space 100 or more.
100 or more*
Wall
Wa
ll
<Space required for installation and servicing>
4
Installation
CAUTION
CAUTION
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put any heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering
cloth or other material to not damage the unit.
• To move the indoor unit, hold the bottom face of the unit only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, resin parts or other parts).
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
Install an indoor unit as described below.
1
Prior to piping or electric work, remove the air intake grille.
(Push down the upper part slightly and pull it toward you.)
2
Remove the front panel.
(Fixing screws at right and left sides of the lower side)
3
Remove the fan guard. (Fixing screws at right, center and left sides)
4
Start piping and wiring works.
5
Keep the front space of the indoor unit as wider as possible.
A wide space is required for maintenance and service works and then it is useful for distributing cool / hot air
in the room resulted in increase of cooling / heating effect.
6
Install the indoor unit horizontally or slanting a little rightward viewed from the front side.
Fan guard screws
<Good installation>
<Poor installation>
Front panel screws
15-EN
16-EN
Summary of Contents for MML-UP0071H-E
Page 30: ...EB99841101 ...