Installation Manual
9
APPLICABLE CONTROLS
REQUIREMENT
When the air conditioner is used for the
fi
rst time, it will
take some moments after the power has been turned
on before the remote controller becomes available for
operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses
(The automatic addresses are set up by performing
operations on the outdoor interface circuit board.)
While the automatic addresses are being set up, no
remote controller operations can be performed.
Setup takes up to 10 minutes (usually about
5 minutes).
• When the power is turned on after automatically
address setup, it takes up to 10 minutes (usually about
3 minute) for the outdoor unit to start operating after
the power has been turned on.
Before the air conditioner was shipped from the factory,
all units are set to [STANDARD]
(factory default).
If necessary, change the indoor unit settings.
The settings are changed by operating the wired remote
controller.
* The settings cannot be changed using only a wireless
remote controller and simple remote controller by itself
so install a wired remote controller separately as well.
Applicable controls setup
(settings at the site)
Remote controller model name:
RBC-ASC11E
Basic procedure
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
CAUTION
Set only the Code No. shown in the following table:
Do NOT set any other Code No.
If a Code No. not listed is set, it may not be possible
to operate the air conditioner or other trouble with the
product may result.
1
Push and hold menu button and [ ]
setting button simultaneously for
10 seconds or more.
• After a while, the display
fl
ashes as shown in
the
fi
gure. “ALL” is displayed as indoor unit
numbers during initial communication
immediately after the power has been turned on.
Indoor unit No.
2
Each time [ ] [ ] setting button is pushed,
indoor unit numbers in the group control
change cyclically. Select the indoor unit to
change settings for.
• The fan of the selected indoor unit runs.
The indoor unit can be con
fi
rmed for which to
change settings.
3
Push OFF timer button to con
fi
rm the selected
indoor unit.
Set data
Code No.
4
Push the menu button to make Code No.
[
]
fl
ash. Change Code No. [
] with
[ ] [ ] setting button.