background image

– 18 –

Selecting swing type

1. Push 

 for 4 seconds or more when the air 

conditioner is not working.

 flashes.

Indicates CODE No. [F0].

2. Select an indoor unit to be set by pushing 

 

(left side of the button).
Each time you push the button, unit numbers 
change as follows:

The fan of the selected unit runs and the louvers 
start swinging.

3. Select a swing type by pushing “TIME” 

 

 

buttons.

 

 

CAUTION

CAUTION

Do not set the swing SET DATA to “

0000

”.

(This setting may cause a failure of the louvers.)

About “Dual swing”

“Dual” means that louvers 

01

 and 

03

 are directed 

and swing in one direction and louvers 

02

 and 

04

 are 

directed and swing in the opposite direction.
(When louvers 

01

 and 

03

 are directed downward, 

louvers 

02

 and 

04

 are directed horizontally.)

About “Cycle swing”

The four louvers swing independently at respective 
timings.

4. Push  

button.

5. Push 

 button to complete the setting.

Swing SET DATA

Swing of louvers

0001

Standard swing

(Factory default)

0002

Dual swing

0003

Cycle swing

No 

display

UNIT No. 

1-1

UNIT No. 

1-2

UNIT No. 

1-3

UNIT No. 

1-4

Swing SET DATA

04

02

03

01

Drain pipe

Refrigerant pipe

Locking the louvers 
(No swing)

1. Push 

 (right side of the button) for 4 seconds 

or more when the air conditioner is not working.

 flashes.

Indicates CODE No. [F1].

2. Select an indoor unit to be set by pushing 

 

(left side of the button).
Each time you push the button, unit numbers 
change as follows:
The fan of the selected unit runs and the louvers 
start swinging.

3. Select a louver you want to lock by pushing “TEMP.” 

  

buttons.

4. Select the wind direction of the louver you do not 

want to swing by pushing “TIME” 

 

 buttons.

* When (4) or (5) is selected, dew drop may occur 

during cooling mode.

5. Determine the setting by pushing 

 button.

When the setting has been determined, 

 lights 

up.

6. Push 

 button to complete the setting.

Cancelling louver lock

Set the wind direction to “

0000

” of the louver lock setup 

procedure above.

• When the setting is canceled, 

 goes out.

Other operations are the same as those in 
“Locking the louvers (No swing)”.

Remote controller sensor

The temperature sensor of the indoor unit senses room 
temperature usually. Set the remote controller sensor 
to sense the temperature around the remote controller.
Select items following the basic operation procedure 
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

 ).

• Specify [32] for the CODE No. in Procedure 

3

.

• Select the following data for the SET DATA in 

Procedure 

4

.

When 

 flashes, the remote controller sensor is 

defective.
Select the SET DATA [0000] (not used) or replace the 
remote controller.

Group control

In a group control, a remote controller can control up to 
maximum 8 units.
• The wired remote controller only can control a group 

control. The wireless remote controller is unavailable 
for this control.

• For wiring procedure and wires of the individual line 

(Identical refrigerant line) system, refer to “Electrical 
Connection” in this Manual.

• Wiring between indoor units in a group is performed 

in the following procedure.

• Connect the indoor units by connecting the remote 

controller wires from the remote controller terminal 
blocks (A, B) of the indoor unit connected with a 
remote controller to the remote controller terminal 
blocks (A, B) of the other indoor unit. (Non-polarity)

• For address setup, refer to the Installation Manual 

attached to the outdoor unit.

UNIT No. 

1-1

UNIT No. 

1-2

UNIT No. 

1-3

UNIT No. 

1-4

(1)

0001

(2)

0002

(3)

0003

(5)

0005

(4)

0004

SET DATA

0001-0005 

(Louver lock position code)

SET DATA

0000

0001

Remote controller 

sensor

Not used 

(Factory default)

Used

0000

Setting data

35-EN

36-EN

Summary of Contents for MMU-AP0057MH-E

Page 1: ...h Indoor Unit Model name Compact 4 way Cassette type MMU AP0057MH E MMU AP0077MH E MMU AP0097MH E MMU AP0127MH E MMU AP0157MH E MMU AP0187MH E AIR CONDITIONER MULTI TYPE Installation Manual For commercial use ...

Page 2: ...ation Manual attached to the outdoor unit ADOPTION OF R410A REFRIGERANT This Air Conditioner uses R410A an environmentally friendly refrigerant Contents 1 Precautions for safety 3 2 Accessory parts 7 3 Selection of installation place 7 4 Installation 9 5 Drain piping 11 6 Refrigerant piping 13 7 Electrical connection 14 8 Applicable controls 16 9 Test run 19 10 Maintenance 20 11 Troubleshooting 21...

Page 3: ... or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba C...

Page 4: ...ferent from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Before opening the intake grille of the indoor unit or service panel of the outdoor unit set the circuit breaker to the OFF position Failure to set the circuit breaker to the OF...

Page 5: ...ce any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation When the indoor unit is to be suspended the designated hanging bolts M10 or W3 8 and nuts M10 or W3 8 must be used Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough...

Page 6: ... the power is turned on without first conducting these checks If there is any kind of trouble such as check code display has appeared smell of burning abnormal sounds the air conditioner fails to cool or heat or water is leaking has occurred in the air conditioner do not touch the air conditioner yourself but set the circuit breaker to the OFF position and contact a qualified service person Take s...

Page 7: ... water dust former refrigerant or refrigerating oil enter the refrigerating cycle during installation work To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the R410A refrigerant For conne...

Page 8: ...ng places Place exposed to air with high salt content seaside area or place exposed to large quantities of sulfide gas hot spring The unit should be used in these places special protective measures are needed A restaurant kitchen where a lot of oil is used or place near machines in a factory Oil adhering to the heat exchanger and resin part turbo fan in the indoor unit may reduce the performance g...

Page 9: ... 200 200 15 or more 271 or more 1000 or more 271 or more 1000 or more 1000 or more An obstacle 15 or more 1 400 or more 560 or more 3 Check port 450 2 Check port 450 1000 or more Ceiling height Unit m When the height of the ceiling exceeds the distance of the item Standard 4 way in below table the warm air is difficult to reach the floor It is necessary to change the setup value of the high ceilin...

Page 10: ...nel external dimension 620 13 to 20 13 to 20 Ceiling open dimension 580 to 594 Panel external dimension 620 External view Unit mm 23 5 0 146 191 95 147 105 55 235 105 235 320 214 256 93 40 132 173 257 70 Ø162 53 193 154 146 8 3 12 184 156 ØA Ceiling open dimension 580 to 594 Bottom face of ceiling Wiring entry for remote control Unit external dimension 575 Refrigerant pipe connecting port Gas side...

Page 11: ...ccording to size in the unit external view as shown below Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Indoor unit Panel fixing screw Installation pattern Accessory Installation pattern attachment hole New concrete slab Install the bolts with insert brackets or anchor bolts Steel flame structure Use existing angles or install new support angles Existing concrete slab Use a hole in a...

Page 12: ... le s s 5 Drain piping CAUTION CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained and apply a heat insulation so as not to cause a dew drop Inappropriate piping work may result in water leakage in the room and wet of furniture Piping Heat insulating material Require the following materials for piping and heat insulating at site Flexible hose U...

Page 13: ...36 mm or less Underside of ceiling Indoor unit 300 mm or less Rising up 850 mm or less After the electric work has finished pour water during COOL mode operation If the electric work has not yet finished pull out the float switch connector CN34 Red from the electrical control box and check draining by plugging the single phase 220 240 V power to the terminal blocks R L and S N If doing so the drai...

Page 14: ...f R410A is higher than that of R22 Approx 1 6 times Use a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak but also a trouble of the refrigeration cycle Align the centres of the connecting pipes and tighten the flare nut as far as possible with your fingers Then...

Page 15: ...e power supply wires refer to the Installation Manual attached to the outdoor unit Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Arrange the power supply circuit breaker and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used Power supply wire specification Cab...

Page 16: ...ovided for the control wire and remote controller wire Do not connect the high voltage circuit 1 Loosen the two screws and remove the cover of electrical control box by sliding in the direction of the arrow 2 Connect the power supply wire communication wires and remote controller wire to the terminal block of the electrical control box 3 Tighten the screws of the terminal block and fix the wires w...

Page 17: ...face circuit board While the automatic addresses are being set up no remote controller operations can be performed Setup takes up to 10 minutes usually about 5 minutes When the power is turned on after automatic address setup It takes up to 10 minutes usually about 3 minutes for the outdoor unit to start operating after the power has been turned on Before the air conditioner was shipped from the f...

Page 18: ...g to 0001 or 0003 is possible however setting to 0000 requires a setting data change to 0000 using the wired remote controller separately sold with the normal switch setting factory default To restore the factory defaults To return the DIP switch settings to the factory defaults set SW501 1 and SW501 2 to OFF connect a separately sold wired remote controller and then set the data of CODE No 5d to ...

Page 19: ...ing cooling mode 5 Determine the setting by pushing button When the setting has been determined lights up 6 Push button to complete the setting Cancelling louver lock Set the wind direction to 0000 of the louver lock setup procedure above When the setting is canceled goes out Other operations are the same as those in Locking the louvers No swing Remote controller sensor The temperature sensor of t...

Page 20: ...he status returns to a normal 2 4 3 1 5 Wireless remote controller RBC AX32UW series 1 Turn on the power of the air conditioner When power is turned on for the first time after installation it takes approx 5 minutes until the remote controller becomes available In the case of subsequent power on it takes approx 1 minute until the remote controller becomes available Execute a test run after the pre...

Page 21: ...ter away from the grille and remove 8 1 7 Hook Fall preventive strap 4 Cleaning with water or vacuum cleaner If dirt is heavy clean the air filter using tepid water with a neutral detergent or just water After cleaning with water dry the air filter sufficiently in a shaded place 5 Mount the air filter 6 Close the air intake grille Check that the fall preventive strap of the air intake grille is at...

Page 22: ...ures when abnormal sound is generated Filter Indoor Dust dirt breakage Wash the filter with water when it is contaminated Replace it when it is damaged Fan Indoor Vibration balance Dust dirt appearance Replace the fan when vibration or balance is terrible Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are ...

Page 23: ...nication trouble between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 Communication circuit trouble between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit trouble between indoor outdoor unit Detected at outdoor unit side ...

Page 24: ...H03 01 Comp 1 side 02 Comp 2 side Current detect circuit system trouble IPDU H05 H05 TD1 sensor miswiring I F H06 H06 Low pressure protective operation I F H07 H07 Oil level down detective protection I F H08 H08 01 TK1 sensor trouble 02 TK2 sensor trouble 04 TK4 sensor trouble 05 TK5 sensor trouble Oil level detective temp sensor trouble I F H15 H15 TD2 sensor miswiring I F H16 H16 01 TK1 oil circ...

Page 25: ... unit address ALT Indoor unit overflow trouble Indoor unit P12 ALT Indoor unit fan motor trouble Indoor unit P13 P13 ALT Outdoor liquid back detection trouble I F P15 P15 01 TS condition 02 TD condition ALT Gas leak detection I F P17 P17 ALT Discharge temp TD2 trouble I F P19 P19 Detected outdoor unit number ALT 4 way valve inverse trouble I F P20 P20 ALT High pressure protective operation I F P22...

Page 26: ...ouble 1B All Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending trouble in TCC LINK central control device TCC LINK C06 Receiving trouble in TCC LINK central control device TCC LINK C12 Batch alarm of general purpose equipm...

Page 27: ...RPORATION 336 Tadehara Fuji shi Shizuoka ken 416 8521 JAPAN TCF holder TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMU AP0057MH E MMU AP0077MH E MMU AP0097MH E MMU AP0127MH E MMU AP0157MH E MMU AP0187MH E Commercial name Super Modular Multi System Air Conditioner Super Heat Recov...

Page 28: ... STANDARD 0001 HIGH CEILING 2 0002 HIGH CEILING 3 0003 High ceiling setup CODE NO 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 2 0002 HIGH CEILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 NO CHANGE NONE...

Page 29: ...EB99813301 ...

Reviews: