– 23 –
45-EN
46-EN
F01
—
—
ALT
Indoor unit TCJ sensor trouble
Indoor unit
F02
—
—
ALT
Indoor unit TC2 sensor trouble
Indoor unit
F03
—
—
ALT
Indoor unit TC1 sensor trouble
Indoor unit
F04
F04
—
ALT
TD1 sensor trouble
I/F
F05
F05
—
ALT
TD2 sensor trouble
I/F
F06
F06
01: TE1 sensor
02: TE2 sensor
ALT
TE1 sensor trouble
TE2 sensor trouble
I/F
F07
F07
01: TL1 sensor
02: TL2 sensor
03: TL3 sensor
ALT
TL1,TL2 or TL3 sensor trouble
I/F
F08
F08
—
ALT
TO sensor trouble
I/F
F10
—
—
ALT
Indoor unit TA sensor trouble
Indoor unit
F12
F12
01: TS1 sensor
03: TS3 sensor
ALT
TS1 or TS3 sensor trouble
I/F
F13
F13
01: Comp. 1 side
02: Comp. 2 side
ALT
TH sensor trouble
IPDU
F15
F15
—
ALT
Outdoor unit temp. sensor miswiring (
ТЕ
, TL)
I/F
F16
F16
—
ALT
Outdoor unit pressure sensor miswiring (Pd, Ps)
I/F
F23
F23
—
ALT
Ps sensor trouble
I/F
F24
F24
—
ALT
Pd sensor trouble
I/F
F29
—
—
SIM
Indoor unit other trouble
Indoor unit
F30
F30
—
SIM
Occupancy sensor trouble
Indoor unit
H01
H01
01: Comp. 1 side
02: Comp. 2 side
Compressor break down
IPDU
H02
H02
01: Comp. 1 side
02: Comp. 2 side
Compressor trouble (lock)
IPDU
H03
H03
01: Comp. 1 side
02: Comp. 2 side
Current detect circuit system trouble
IPDU
H05
H05
—
TD1 sensor miswiring
I/F
H06
H06
—
Low pressure protective operation
I/F
H07
H07
—
Oil level down detective protection
I/F
H08
H08
01: TK1 sensor trouble
02: TK2 sensor trouble
04: TK4 sensor trouble
05: TK5 sensor trouble
Oil level detective temp sensor trouble
I/F
H15
H15
—
TD2 sensor miswiring
I/F
H16
H16
01: TK1 oil circuit system trouble
02: TK2 oil circuit system trouble
04: TK4 oil circuit system trouble
05: TK5 oil circuit system trouble
Oil level detective circuit trouble
I/F
L02
L02
—
SIM
Model mismatch of indoor and outdoor unit
I/F
L03
—
—
SIM
Indoor unit centre unit duplicated
Indoor unit
L04
L04
—
SIM
Outdoor unit line address duplicated
I/F
L06
L06
No. of indoor units with priority
SIM
Duplicated indoor units with priority
(Displayed in unit other than indoor unit with priority)
I/F
L07
—
—
SIM
Group line in individual indoor unit
Indoor unit
L08
L08
—
SIM
Indoor unit group/Address unset
Indoor unit, I/F
L09
—
—
SIM
Indoor unit capacity unset
Indoor unit
Check code
Wireless remote controller
Check code name
Judging device
Wired remote
controller display
Outdoor unit 7-segment display
Sensor block display of receiving unit
Auxiliary code
Operation
Timer
Ready
Flash
Summary of Contents for MMU-AP0057MH-E