– 13 –
1. SPECIFICATIONS
Compact 4-Way Cassette Type
(*1) Cooling / heating capacity is based on single connection operation with standard piping length under
Japanese Industrial Standard B 8615 Condition 1.
(*2) Remote controller and ceiling panel are sold separately
(*3) Height from the ceiling.
(*4) Depth doesn't including the Electric parts box.
䋨䋨
50/60Hz
䋩
Model name
MMU-AP0057MH-E/-TR
MMU-AP0077MH-E/-TR
MMU-AP0097MH-E/-TR
Cooling Capacity
䋨
*1
䋩
kW
1.7
2.2
2.8
Heating Capacity
䋨
*1
䋩
kW
1.9
2.5
3.2
Electrical
Power supply
1phase 50Hz 230V(220V-240V) /1phase 60Hz 220V
charastaristics
䋨
Separate power supply for indoor units is required.)
Running current
A
0.16
/
0.15
0.23
/
0.21
0.24
/
0.22
Power consumption
kW
0.016
/
0.016
0.023
/
0.023
0.025
/
0.025
Starting current
A
0.28
/
0.27
0.41
/
0.38
0.43
/
0.39
Appearance
Main Unit
Zinc hot dipping steel plate * Heat-insulating material attached to only upper plate
Ceiling Panel Model Name
RBC-UM21PG(W)-E
䋨
*2
䋩
Panel Color
Gran White (Mansell 5PB9/1)
Outer
Main Unit
Height
䋨
*3
䋩
mm
256
dimension
Width
mm
575
Depth
䋨
*4
䋩
mm
575
Ceiling Panel Height
䋨
*3
䋩
mm
12
Width
mm
620
Depth
mm
620
Total weight
Main Unit
kg
15
Ceiling Panel
kg
2.5
Heat exchanger
Finned tube
Soundproof/Heat-insulating material
Non-flammable insulation
Fan
Turbo fan
Fan unit
Standard air flow ( M+ / M / L+ / L )
m
3
/h
430(415/400/385/365)
552(500/462/395/378)
570(520/468/395/378)
Motor
W
60
Air filter
Standard filter (Long life filter)
Controller
䋨
*2
䋩
Remote controller
Connecting
Gas side
mm
Ø
9.5
pipe
Liquid side
mm
Ø
6.4
Drain port (Nominal dia. mm)
VP20 (Polyvinyl chloride tube)
Sound pressure level High ( M+ / M / L+ / L )
dB
32 ( 31 / 30 / 29 / 29 )
37 ( 34 / 33 / 30 / 29 )
38 ( 35 / 33 / 30 / 29 )
Sound power level High ( M+ / M / L+ / L )
dB
47 ( 46 / 45 / 44 / 44 )
52 ( 49 / 48 / 45 / 44 )