DN
Item
Description
At shipment
33
Temperature unit select
0000: °C
0001: °F
0001: °F
External static pressure
High-ceiling adjustment
(Air flow selection)
Refer to next page.
Depending on model
type
5d
60
Timer setting
(wired remote controller)
0000: Available
0001: Unavailable
0000: Available
(can be performed)
(cannot be performed)
77
Dual set point
0000: Unavailable
0002: Available
0000: Unavailable
Alarm output setup of the
header unit
0000: Not including the state
of following unit
0001: Including the state of
0000: Not including the
79
following unit
state of following
unit
Change unit +0.9°F(0.5°C)
or +1.8°F(1.0°C) on remote
0000 : +0.9°F(0.5°C)
0001 : 1.8°F(1.0°C)
0000 : +0.9°F(0.5°C)
b3
Soft cooling
0000: Unavailable
0001: Available
0001: Available
Occupancy sensor/
Wireless Remote controller
Provided / None
0000: None
0001: Occupancy sensor
0000: None
b5
provided
0002: Wireless remote controller provided
Occupancy sensor
Enable / Invalid
(Absence time judgment
time)
0000: Invalid
0001: 30min.
0002: Enable
b6
0002: 60min.
0004: 120min.
(60 min.)
0005: 150min.
b7
Occupancy sensor
operation at absent time
0000: Stand by
0001: operation stop
0000: Stand by
CF
4-way cassette type model
name
0000: Standard Model
0001: larger case model
Depending on model
type
Whether the power
saving mode can be set
by the remote controller
0000: Invalid
0001: Valid
0001: Valid
d0
E0
Destination
0000: Japan
000
1
:
North American
000
1
:
North American
000
3
:
China
E6
Wireless remote
controller A-B selection
0000: A
0001: B
0000: A
Swing mode
0000 : Out of sync swing
0002 : Dual swing
0001 :
Standard
0003 : Cycle swing
0001 : Standard
F0
Presence of Application
control kit
0000: None
0001: Exist
0000: None
F6
7
A
000
4
:
Global
Remote controller
0000:
Use
0001:
Do not use
0000:
Use
103
•
Indoor unit production after Jun-2021 does not need this
DN setting. The serial number is 12600001 or upper.
- 39 -