<Indoor unit address>
5
Push the TEMP.
/
buttons repeatedly to set the CODE No. to
13
13
13
13
13
.
6
Push the TIME
/
buttons repeatedly to set an indoor unit address.
7
Push the
button.
(It is OK if the display turns on.)
<Group address>
8
Push the TEMP.
/
buttons repeatedly to set the CODE No. to
14
14
14
14
14
.
9
Push the TIME
/
buttons repeatedly to set a group address. If the indoor unit is
individual, set the address to
0000
0000
0000
0000
0000
; header unit,
0001
0001
0001
0001
0001
; follower unit,
0002
0002
0002
0002
0002
.
Individual
: 0000
Header unit
: 0001
Follower unit
: 0002
10
Push the
button.
(It is OK if the display turns on.)
11
Push the
button.
The address setting is complete.
(
SETTING
flashes. You can control the unit after
SETTING
has disappeared.)
}
In case of group control
<RBC-AMS5*E-UL>
1
Push the [
MENU] button to
display the menu screen.
MENU]
2
Push and hold the [
button and the [
] button
at the same time to display the
“Field setting menu”.
→
Push and hold the buttons for
more than 4 seconds.
When the group control is used, the fan and louver
of the selected indoor unit operate.
(Line address)
<
<” [
F1
F1] button, then set “
0012
” with the
→
Move the cursor to select “Code(DN)” with the “
[
] / [
] button.
→
Move the cursor to select “Data” with the “
>
>” [
F2
F2] button, then set
Line address
“Data” with the [
] / [
] button.
3
Push the [
] / [
] button to select
“7. DN setting” on the “Field setting menu”
S
et
Set” [
F2
screen, then push the “
F2] button.
→
The fan and louver of the indoor unit operate.