8
-5. Diagnostic Procedure for Each Check Code (Indoor Unit)
Yes
Yes
No
Yes
Yes
Yes
No
Yes
No
No
No
No
[E01]
Check code
Check code name
Cause
Communication trouble between
the indoor unit and remote
controller (detected on the remote
controller)
1. Remote controller inter-unit wire trouble
2. Indoor power trouble
3. Indoor P.C. board trouble
4. Remote controller address setup trouble
5. Remote controller P.C. board trouble
Is the
inter-unit wire of
remote controllers (A/B)
normal?
Is the
connector on the
harness or the harness
from terminal block of
indoor unit connected
correctly?
Is a group control
operation?
Is power of each indoor
unit turned on?
Is power applied
to remote controller?
AB terminals: Approx.
DC18V
Is one of two
remote controllers
set as a header unit?
Correct inter-unit cable of
remote controller.
Correct connector connection
and check circuit wiring.
Check power connection
status of indoor unit. (Turn on
power again.)
Replace indoor P.C. board.
Replace remote controller.
Change one to header/other to
follower. (Remote controller
address connector)
Check code
Check code name
Cause
Check code
Check code name
Cause
* The check code is not indicated on the central control device or the 7-segment indication on the outdoor unit.
Yes
No
[E02]
[E03]
Signal transmission trouble on the
remote controller
Communication trouble between
the indoor unit and remote
controller controller
(detected on the indoor unit)
Unable to send signals to indoor units
No communication from the remote
controller/communication adapter
The
communication wiring
between the remote
controller and indoor units
is connected properly.
Connect the wiring properly.
The transmission circuit in the
remote controller malfunctions.
Replace the remote controller.
The trouble is detected when the indoor unit cannot receive the signal from the wired remote controller.
Check the communication wiring from the remote controller A and B.
The check code [E03] is not indicated on the remote controller as its communication is down.
However, the code is indicated on the
central controller.
- 82 -