[E04]
Check code
Check code name
Cause
Indoor/Outdoor communication
circuit trouble
(Detected at indoor side)
1.
Power of outdoor unit was firstly turned on.
2.
Connection trouble of communication line between
indoor and outdoor
3.
Terminator resistor setup trouble on
communication between indoor and outdoor
4.
Address setup trouble
W
as power turned on
in order of indoor unit
outdoor unit?
Is connection
(U1/U2 terminals) of
indoor/outdoor inter-unit
wire normal?
Is connector
connection from U1/U2
terminals of indoor/outdoor
inter-unit wire
normal?
Is the terminator resistor
setup of outdoor unit
normal?
Is power applied to fuse
(F03) on indoor P
.C.
board?
Is address setup correct?
Is there noise, etc?
T
urn on power again in order
of indoor unit
outdoor unit.
Correct inter-unit wire.
Check connection of inter-unit
wire between indoor and outdoor
is correct, and then connect
communication line connector on
indoor P.C. board (CN40) to
CN44 (EMG).
Correct the terminator resistor
setup.
Set up address again.
Replace the fuse.
Check noise, etc, and
eliminate it if any
.
Replace indoor P
.C. board.
Ye
s
Ye
s
No
No
Ye
s
No
[E08]
Sub-code: Duplicated indoor address
Check code
Check code name
Cause
Duplicated indoor addresses
Indoor addresses are duplicated.
Is wire connection to
communication line
normal?
Is communication line
connected to the specified
outdoor unit ?
Is indoor unit quantity
connected to outdoor
unit correct?
Correct wire connection.
Correct communication line.
Set up indoor address again.
Using a wired remote controller, check the setup CODE No. (DN code)
12, 13, and 14.
When there is no address duplication, check to the following flowchart.