[F03]
Check code
Check code name
Cause
Indoor
TC1 sensor trouble
TC1 sensor Open/Short-circuit
Is TC1
sensor connector
(CN100: Brown) on indoor
P
.C. board normally
connected?
Are characteristics
of
TC1 sensor resistance
value normal?
Correct connection of
connector
.
Replace TC1
sensor
.
Replace indoor main P
.C. board.
* See
“Indoor unit temperature
sensor characteristics” on “9-6. SensorCharacteristics”.
[F10]
Check code
Check code name
Cause
Indoor TA
/TSA
sensor trouble
T
A
sensor Open/Short-circuit
This trouble code
means detection
of Open/Short-circuit of TA
sensor. Check disconnection of circuit for connection
of connector (TA /TSA sensor :
CN104, Yellow) and characteristics of sensor resistance value.
(See “Indoor unit
temperaturesensor characteristics” on “9-6. Sensor Characteristics”.)
If
se
nso
r is
nor
m
al
, re
place
ind
oo
r P
.C
.
b
oa
rd
.
[F29]
(Power ON)
(Repetition)
(Approx. 3 minutes)
(Approx. 1 minute)
Indoor other trouble
Indoor P
.C. board trouble
This trouble is detected during operation of air conditioner of IC10 non-volatile memory (EEPROM) on
indoor unit P
.C.board. Replace service P
.C. board.
* If EEPROM was not inserted when power was turned on or it is absolutely impossible to read/write
EEPROM data, the automatic address mode is repeated.
[SET
DA
T
A]
is displayed
on remote
controller
.
[SET
DA
T
A]
disappears.
LED (D02) 1Hz
flashes for approx.
10 seconds on
indoor unit P
.C.
board.
Reboot (Reset)
Check code
Check code name
Cause
[F30]
Check code
Check code name
Cause
Occupancy sensor trouble
1.Occupancy sensor trouble
2. Indoor P.C. board trouble
(4-way cassette type)
Is connection
of the occupancy
sensor connector
(CN214) nor
mal?
Correct the connector
connection.
Is DN code [B5] setup?
By the wired remote
controller
, change the
enab
le DN code [B5] from
[0000]
→
[0001]
Replace the indoor
P
.C
. board (MCC-1643).
NO
YES
Is the Occupancy
sensor unit nor
mal?
Replace the Occupancy
sensor unit
NO
YES
NO
YES
- 86 -