Ye
s
Ye
s
No
No
[L30]
Check code
Cause
Abnormal input from the outside
Check code name
Interlock in indoor unit from
outside
Is outside
device connected
to connector?
Does the
outside device
correctly operate even
if indoor unit with the
outside device is
turned off?
Does outside device
correctly operate?
Replace intdoor P.C.board.
Replace outside device.
Ye
s
No
Replace outdoor P.C. board.
Replace indoor P.C. board
Ye
s
Ye
s
Ye
s
Ye
s
No
No
No
Ye
s
No
No
No
Ye
s
* Check there is 220V-240V voltage of 1-3 pin of CN504 on indoor P.C. board.
[P10]
Sub-code: Overflowing indoor unit's address
Cause
Check code
Is float SW
connector (Indoor
control P
.C. board
CN34) connected
normally?
Does float SW
operate?
Is wiring normal?
Does drain pump
operate?
Is there a trap in
the drainage route?
Is power supply to
drain pump normal?*
Correct connector connection.
Check and correct wiring.
Check indoor P
.C. board.
Failure
Replace
Check indoor P
.C. board.
Failure
Improve the trap section
Replace
Replace drain pump.
Improve the clogged
drain pipe.
Check code name
W
ater overflow in an indoor unit
1. Float
SW
malfunction
2. Drain
pump
malfunction
3.
Clogging of drain pipe
4. Indoor
P
.C.
board
trouble
- 88 -