89
[IPDU in S-MMS standard outdoor unit detects: Representative example]
Check code display
(
∗
)
¡
: Goes on,
¥
: Flashes,
l
: Goes off
A (Alternate)
: Flashing condition is alternate when there are two flashing LED.
S (Simultaneously) : Two LED flash simultaneously when there are two flashing LED.
Note) The above check codes are the representative examples and they differ according to the combined outdoor units (SHRM, etc.).
For details, refer to the service guide for the corresponding outdoor unit.
Outdoor 7-segment
Auxiliary code
F13
01: Compressor 1 side
02: Compressor 2 side
H01
01: Compressor 1 side
02: Compressor 2 side
H02
01: Compressor 1 side
02: Compressor 2 side
H03
01: Compressor 1 side
02: Compressor 2 side
P04
01: Compressor 1 side
02: Compressor 2 side
P07
01: Compressor 1 side
02: Compressor 2 side
04: rpm difference error
06: Max. rpm over
08: Out of step
P22
0A: Idc lock
0C: Fan lock
0d: Lock
0E: Synchronous error
0F: Braking error
P26
01: Compressor 1 side
02: Compressor 2 side
P29
01: Compressor 1 side
02: Compressor 2 sid
TCC-LINK central
& remote controller
F13
H01
H02
H03
P04
P07
P22
P26
P29
AI-NET central
(Network adapter use)
43
1F
1d
17
21
1C
1A
14
16
Sensor lamp display
Block display (
∗
)
Operation Timer Ready Flash
¥
¥
¡
A
l
¥
l
l
¥
l
l
¥
l
¥
l
¥
A
¥
l
¥
A
¥
l
¥
A
¥
l
¥
A
¥
l
¥
A
Main defective position
Outdoor IGBT incorporated temp. sensor (TH)
error
Compressor break-down
Compressor error (Lock)
Current detection circuit error
High pressure SW system operation
Heat sink overheat error
IPDU error for outdoor fan
G-Tr (IGBT) short-circuit protective error
Compressor position detection circuit system
error
Description
When open/short of outdoor IGBT incorporated temp. sensor
(TH) was detected
When inverter current (Idc) detection circuit detected over-current
When lock of compressor was detected
Defective current was detected during stop of compressor.
High pressure SW operated.
Outdoor IGBT incorporated temp. sensor (TH) detected high temp. error.
IPDU for outdoor fan detected each error.
Short-circuit protective operation (Instantaneous over-current) of
compressor motor drive circuit element worked.
Position detect error of compressor motor was detected.